- 207 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Function
2.4 Stopping operation
2.4.1 Stopping operation on cooling mode
2.4.2 Stopping operation on heating mode
Inv Compressor
Fan
Main EEV
4 way valve
Subcooling EEV
0 Hz
0 Hz
Full open
On
Full close
Full close
Operation
Component
After 15 min from stop, min.
After 15 min from stop, off
Note
Sub unit
compressor
Off
Hot gas bypass
On
After 15 min from stop, Off
Inv Compressor
Fan
Main EEV
4 way valve
Subcooling EEV
0 Hz
0 Hz
Full open
Off
Full close
Full close
Operation
Component
After 15 min from stop, min.
Off
-
-
-
-
-
-
Note
Sub unit
compressor
Off
Hot gas bypass
On
After 15 min from stop, Off