Function
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
■
High pressure control
■
Low pressure control
3. Protection control
Stop
Stop
Pd
≥
3676 kPa
Off
Normal control
Pd < 3284 kPa
Normal control
Frequency holding
Pd
≥
3284 kPa
+10Hz/2sec.
-5Hz/2sec.
Pd > 3546 kPa
Hot gas
Fan
Compressor
Pressure Range
Frequency
holding
Normal control
Ps
≤
242 kPa
Off
Normal control
Ps
≥
399 kPa
On
-10Hz/2sec.
-5 Hz/2sec.
Ps
≤
229 kPa
before 1min
Stop
Stop
Ps
≤
229 kPa
after 1min
Hot gas
Fan
Compressor
Pressure Range