Function
3.2 Discharge temperature control
■
Outdoor unit control
■
Indoor unit control
3.3 Inverter protection control
Emergency
SH control
System stop
103˚C < Tdis
≤
115˚C
Tdis >115 ˚C
Temperature range
EEV
Keep current control
98 ˚C < Tdis
≤
103 ˚C
SH control
Tdis
≤
98 ˚C
Frequency down +
const. Comp off
Liquid injection on
No frequency up
System stop
105˚C< Tdis
≤
112 ˚C
Tdis >115˚C
Temperature range
Compressor
On
Liquid injection
98 ˚C < Tdis
≤
103 ˚C
Keep
state
Pressure control
Tdis
≤
98˚C
Off
Max. limit
350 pulse
Subcooling EEV
If liquid is on,
Max. limit
350 pulse
Max. limit
150 pulse
Pressure control
Tdis >95 ˚C
Off
10 pulse open /10sec
System stop
Current 20A
item
control
Inv compressor 5Hz down/10 sec
Current 20A
Inv. compressor no frequency up
Current 18A
Inv. Compressor normal control
Current 18A
System stop
DC Peak
System stop
High pressure switch
System stop
Low voltage
<
<
<
<