3.4 Liquid back control
■
Main unit on cooling mode
■
Sub unit on cooling mode
■
Main unit on heating mode
■
Sub unit on heating mode
❇
The logic starts after 9 min. on heating mode and 4 min. on cooling mode from the compressor running.
Tdis < Tc + 12˚C
Discharge temperature
Indoor unit ’s EEV
Normal SH control
Tdis > Tc + 16 ˚C
SH increasing control
Tdis < Tc + 12˚C
Discharge temperature
Indoor unit’s EEV
Normal SH control
Tdis > Tc + 16 ˚C
SH increasing control
SH increasing control
Tdis < Tc + 17˚C
Discharge temperature
Outdoor unit ’s EEV
Normal SH control
Tdis > Tc + 18 ˚C
Normal operation
Tdis < Tc + 17˚C
Discharge temperature
Indoor unit’s EEV
Normal operation
Tdis > Tc + 18 ˚C
Function