4.3 Emergency operation
- If a compressor is out of order, the system can be run except the defective compressor by backup function.
- There are two backup modes. One is the backup of constant speed compressor, and the other is the backup of
inverter compressor.
- In inverter compressor backup mode, there is a restriction on the capacity of the running indoor units. In case of
inverter failure, backup operation is possible when 110kBtu/hr. or more indoor units are ON.
- On the case of single outdoor unit, the required indoor operating capacity is 70kBtu/hr.
- Under the limit capacity in inverter backup mode, outdoor unit will not be run even indoor units are still running.