- 234 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Checking Method for Key Components
EEV
M
1
3
2
6
4
ø5
Red
White
Yellow
Orange
Blue
5
4
3
2
ø4
DC 12V
Driving
circuit
ø3
ø2
ø1
1
ø4
ø3
ø2
ø1
• Pulse signal output value and valve operation
• Output pulse sequence
- In valve close state: 1
→
2
→
3
→
4
→
5
→
6
→
7
→
8
→
1
- In valve open state: 8
→
7
→
6
→
5
→
4
→
3
→
2
→
1
→
8
* 1. If EEV open angle is not change, all of output phase will be OFF
2. If output phase is different or continuously in the ON state, motor will not operate smoothly and start
vibrating.
• EEV valve operation
ø1
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ø2
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ø3
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ø4
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
Output(ø) No.
Output state
1
2
3
4
5
6
7
8
Valve
open
Angle
close
pulse
open
Full open
1350 pulses
- At power ON, open angle signal of 1400 pulses out-
put and valve position is set to
If valve is operated smoothly, no noise and vibration
is occurred and if valve is closed. noise occurs.
- If you contact screw driver to EEV, and contact your
ear to driver hand grip. you can confirm the noise
from EEV.
- If liquid refrigerant is in EEV, the noise is lower.
2.3 Electronic Expansion Valve