Self-diagnosis function
System is off by excessive increase of discharge tempera-
ture of constant speed compressor 1 of sub1 outdoor unit
System is off by excessive increase of discharge tempera-
ture of constant speed compressor 2 of sub1 outdoor unit
System is off by excessive increase of discharge tempera-
ture of constant speed compressor 1 of sub2 outdoor unit
System is off by excessive increase of discharge tempera-
ture of constant speed compressor 2 of sub2 outdoor unit
Failing to receive sub1 signal at main PCB of main outdoor
unit
Failing to receive fan signal at main PCB
Over-current of fan motor (IPM fault)
Low voltage of fan motor driver
Failing to receive main signal at fan PCB
High pressure switch of sub1 outdoor unit is operated by high
pressure rising
Reverse connection or omitting connection of R, S, T power
of sub1 outdoor unit
Failing to receive main signal at main PCB of sub1 outdoor
unit
Liquid pipe temperature sensor of main outdoor unit is open
or short
Subcooling inlet temperature sensor of main outdoor unit is
open or short
Subcooling outlet temperature sensor of main outdoor unit is
open or short
High pressure sensor of sub1 outdoor unit is open or short
Low pressure sensor of sub1 outdoor unit is open or short
Air temperature sensor of sub1 outdoor unit is open or short
Suction temperature sensor of sub1 outdoor unit is open or
short
Discharge temperature sensor of the constant speed com-
pressor 1 of sub1 outdoor unit is open or short
Discharge temperature sensor of the constant speed com-
pressor 2 of sub1 outdoor unit is open or short
Temperature sensor of front-side heat exchanger of sub1
unit is open or short
Discharge temperature of constant
speed compressor 1 of sub1 outdoor
unit
Discharge temperature of constant
speed compressor 2 of sub1 outdoor
unit
Discharge temperature of constant
speed compressor 1 of sub2 outdoor
unit
Discharge temperature of constant
speed compressor 2 of sub2 outdoor
unit
Transmission error : sub1 outdoor unit
➡
main outdoor unit
Transmission error : fan PCB
➡
main
PCB
Over-current of fan motor (IPM fault)
Low voltage of fan motor driver
Transmission error : main PCB
➡
fan
PCB
High pressure switch of sub1 outdoor
unit
Reverse connection of R, S, T power
of sub1 outdoor unit
Transmission error : main outdoor unit
➡
sub1 outdoor unit
Display
Title
Cause of Error
1
0
0
1
0
1
1
0
2
1
0
3
1
0
4
1
0
5
1
0
6
1
0
7
1
0
8
1
0
9
1
1
0
1
1
1
1
1
3
1
1
4
1
1
5
1
1
6
1
1
7
1
1
8
1
2
0
1
2
1
1
2
2
1
2
3
Compressor related errorCompressor related error
Transmission related error
Outdoor unit related error
Liquid pipe temperature sensor of
main outdoor unit
Subcooling inlet temperature sensor of
main outdoor unit
Subcooling outlet temperature sensor
of main outdoor unit
High pressure sensor of sub1 outdoor
unit
Low pressure sensor of sub1 outdoor
unit
Air temperature sensor of sub1 out-
door unit
Suction temperature sensor of sub1
outdoor unit
Discharge temperature sensor of the
constant speed compressor 1 of sub1
outdoor unit
Discharge temperature sensor of the
constant speed compressor 2 of sub1
outdoor unit
Temperature sensor of front-side heat
exchanger of sub1 outdoor unit