Troubleshooting Guide
- 250 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Auto addressing is not done
2. transmission cable is not connected
3. Short circuit of transmission cable
4. Indoor unit transmission circuit fault
05
5. Outdoor unit transmission circuit fault
6. Not enough distance between power and trans-
mission cable?
7. Is the fuse for main PCB power of outdoor unit
burnt out?
Error
No.
Error Type
Error Point
Main Reasons
No signal transmission
between indoor & outdoor
units.
Indoor & Outdoor unit
transmission error
Does all indoor show
this error code CH05?
Is outdoor PCB LED
flickering?
Yes
Yes
No
Is main circuit breaker off?
No
Is not the power
supplied at main terminal
block of outdoor unit ?
Bad connection of power supply cable
Main power supply problem
Yes
No
Yes
No
Outdoor PCB fault
Replace after checking
Re connect transmission cable
No
Yes
Indoor PCB fault
Replace after checking
* If the DC voltage between transmission terminal A, B
of outdoor unit is fluctuate within (-9V~+9V) then
transmission from indoor unit is normal
Is total number of indoor
units connected displayed
after auto addressing?
No
END
* If the DC voltage between transmission terminal A, B
of indoor unit is fluctuate within (-9V~+9V) then
transmission from outdoor unit is normal
Check the insulation of inverter
/ constant compressor and then
replace it
Replace after capacity of
main circuit breaker?
If nothing goes wrong,
Turn on main circuit breaker
Replace outdoor PCB after
checking
Replace TRANS after checking
Replace main PCB fuse after
checking
Replace the PCB of indoor unit
displayed error
Re-connect after check the
transmission cable of indoor
unit displayed error**
Check if the
transmission cable is
properly connected
to indoor / outdoor
terminal block?*
■
Error diagnosis and countermeasure flow chart
Summary of Contents for ARNU07GB1G1