Troubleshooting Guide
- 253 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
11
Indoor unit transmission error
Error
No.
Error Type
Error Point
Main Reasons
Indoor unit doesn’t get sig-
nal from ODU for 3 minutes
continuously
1. Indoor 485 transmission PCB fault
2. After PCB replacing, auto addressing
was not done
■
Error diagnosis and countermeasure flow chart
Yes
No
After Auto addressing,
error code disappears?
Replace indoor unit 485
transmission PCB
No
After ODU main PCB
reset, error code
disappears?
END
Yes
Summary of Contents for ARNU07GB1G1
Page 338: ...P NO 3828A24006P FEBRUARY 2009 ...