Troubleshooting Guide
- 260 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
■
Error diagnosis and countermeasure flow chart
1. Temperature sensor defect of inverter com-
pressor discharge pipe
2. Refrigerant shortage / leak
3. LEV defect
4. Liquid injection valve defect
1. Temperature sensor defect of constant
compressor discharge pipe?
2. Refrigerant shortage/leak
3. LEV defect
4. Liquid injection valve defect
Error
No.
Error Type
Error Point
Main Reasons
Compressor is off
because of over-increase
discharge temperature of
inverter compressor
Compressor is off
because of over-increase
discharge temperature of
constant compressor at
main and sub outdoor unit
Over-increase discharge
temperature of inverter com-
pressor at main outdoor unit
Over-increase discharge
temperature of constant
compressor at main con-
stant outdoor and sub con-
stant outdoor unit
32(Main)
33 (Main)
100,101
(Sub1)
102,103
(Sub2)
152,153
(Sub3)
No
Yes
Is the resistance of discharge
temperature sensor normal?*
Replace discharge
temperature sensor
Is the amount of
refrigerant normal?
[refer refrigerant part]
Weld / reconnect the cracked
portion and recharge refrigerant
Is there pipe crack
or trace of leakage?
Change the amount of
refrigerant
(Charge additive amount)
Is LEV in
outdoor unit normal
at heating operation?
[refer electric
component part]
Replace outdoor unit LEV
Does liquid injection
corresponded
operate normally?
Check liquid injection
corresponded
Is there pipe
(strainer etc.) clogging?
Check another components
and operation conditions
/ Take measures
Replace strainer
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
* Resistance value of discharge temperature sensor
10
°
C = 362k
Ω
, 25
°
C= 200k
Ω
, 50
°
C= 82k
Ω
, 100
°
C= 18.5k
Ω