Troubleshooting Guide
- 263 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Fuse failure
2. Defective noise filter
40
Low current at CT
3. R phase connection problem
4. CT sensor failure (inverter PCB fail-
ure)ure)
Error
No.
Error Type
Error Point
Main Reasons
While inverter compressor
operation R phase current
drops below 2A
■
Error diagnosis and countermeasure flow chart
Is the fuse normal?
[refer electric component part]
No
Replace the fuse
Yes
Is noise filter normal?
[refer electric component part]
No
Replace noise filter
Yes
Replace Inverter PCB
After reset and restart the
system, is CT value (R phase
current) actually less
than 2A?*
Yes
No
Check connection state of
R phase cable and reconnect
* Measure the R phase current with clamp meter