Troubleshooting Guide
- 277 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Refer to CH105
Error No.
Error Type
Error Point
Main Reasons
Transmission error between main
PCB and the Fan PCB (Fan
➔
outdoor, outdoor
➔
Fan)
Transmission error between
main PCB and the Fan PCB
108
Refer to CH24
Error No.
Error Type
Error Point
Main Reasons
Compressor Off due to the high
pressure switch in outdoor unit
Excessive rise of high pres-
sure in outdoor unit
109
(Sub1)
Refer to CH54
Error No.
Error Type
Error Point
Main Reasons
Wrong connection of 3 phase
power cable (Reverse phase /
Phase omission)
Outdoor 3 phase power sup-
ply problem(Reverse phase /
No power in 1 or 2 phase)
110
(Sub1)
Refer to CH104
Error No.
Error Type
Error Point
Main Reasons
104
➔
transmission error between
the outdoor units (Main outdoor
unit is not receiving signal from
Sub units)
147, 149, 171
➔
Sub outdoor units
are not receiving signal from Main
outdoor unit
Transmission error between
outdoor units
111
(Sub1)