Troubleshooting Guide
- 278 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Defective temperature sensor con-
nection
2. Defective temperature sensor
(Open / Short)
3. Defective outdoor unit PCB
Error No.
Error Type
Error Point
Main Reasons
Abnormal sensor resistance value
(Open/Short)
Outdoor unit liquid pipe
(condenser) temperature
sensor error
113 (Main)
125 (Sub1)
137 (Sub2)
166 (Sub3)
1. Defective temperature sensor con-
necter connection
2. Defective temperature sensor
(Open/Short)
3. Defective outdoor PCB
Error No.
Error Type
Error Point
Main Reasons
Abnormal sensor resis-
tance value
(Open/Short)
Outdoor unit sub-cooling
inlet / outlet temperature
sensor error
114 (Main sub-cool inlet)
115 (Main sub-cool outlet)
126 (Sub1 sub-cool inlet)
127 (Sub1 sub-cool outlet)
138 (Sub2 sub-cool inlet)
139 (Sub2 sub-cool outlet)
167 Sub3 sub-cool inlet)
168 (Sub3 sub-cool outlet)
■
Error diagnosis and countermeasure flow chart
Is temperature sensor
connector connections
are normal?
Is the value of temperature
sensor resistance normal?*
Check and correct connection
Replace sensor
Replace outdoor unit PCB
Yes
Yes
No
No
* Sensor resistance 100 k
Ω
over (open) or 100
Ω
below (short) will generate error
Note: Temperate sensor resistance vary with temperature, So compare temperature sensor resistance value
according to outdoor unit temperature by referring below table (±5% tolerance)
Air temperature sensor: 10°C = 20.7k
Ω
: 25°C = 10k
Ω
: 50°C= 3.4k
Ω
Pipe temperature sensor: 10°C = 10k
Ω
: 25°C = 5k
Ω
: 50°C= 1.8k
Ω