Troubleshooting Guide
- 281 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Refer to CH24
Error No.
Error Type
Error Point
Main Reasons
Compressor Off due to the high
pressure switch in outdoor unit
Excessive rise in outdoor
high pressure
140
(Sub2)
Refer to CH54
Error No.
Error Type
Error Point
Main Reasons
Wrong wiring at outdoor unit
(phase reversal / phase omission )
Outdoor 3 phase power
supply problem (Reverse
phase / phase omission)
141
(Sub2)
Refer to CH104
Error No.
Error Type
Error Point
Main Reasons
Transmission error between outdoor units
104 (Main outdoor unit is not receiving sub
outdoor unit s signals)
147, 149, 171 (Sub outdoor units are not
receiving main unit signals)
Transmission error
between outdoor units
142
(Sub2)
Refer to CH34
Error No.
Error Type
Error Point
Main Reasons
Compressor Off due to high pressure
sensor
Excessive rise in high
pressure
143 (Sub1)
145 (Sub2)
Refer to CH35
Error No.
Error Type
Error Point
Main Reasons
Compressor Off due to low pressure sensor
Excessive drop in low
pressure
144 (Sub1)
146 (Sub2)
Refer to CH25
Error No.
Error Type
Error Point
Main Reasons
1. Input Voltage in the installation region
= 3phase 380V±10%
2. Single Phase = 220 ±10%
Low voltage/ High
voltage
147 (Sub1)
149 (Sub2)
Refer to CH49
Error No.
Error Type
Error Point
Main Reasons
Measured value is abnormal (Open/Short)
Outdoor voltage sensing
error
148 (Sub1)
150 (Sub2)