- 31 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Specification
Type
Model
Unit
W
Cooling Capacity
kcal/h
Btu/h
W
Heating Capacity
kcal/h
Btu/h
Casing
Body
mm
Dimensions (W*D*H)
inch
Front Panel
mm
inch
Coil
Rows x Columns x FPI
Face Area
m
2
Type
Motor Output x Number
W
Running Current
A
Fan
Air Flow Rate(H/M/L)
cmm
cfm
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.)
mm
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H/M/L)
dBA±3
Power Supply
Ø / V / Hz
Refrigerant Control
Power cable
Transmission cable
Panel Color
Panel Name(Acc'y)
2Way Ceiling Cassette
ARNU24GTL*1
7,100
6,100
24,200
8,000
6,900
27,300
Galvanized Steel Plate
830x550x225
32.6x21.6x8.9
1050x640x28.5
41.3x25.2x1.1
2x11x20
0.13
Cross Flow Fan
70
0.36
17/15/13
601/530/459
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25.0
28(61.7)
42/37/32
1, 220 ~ 240, 50
1, 220, 60
EEV
CV2.0 X 3C
CVV-SB 1.25 X 2C
Morning fog
PT-HL*
Notes:-
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. EEV : Electronic Expansion Valve
5. To be added for more available Models
* Model Name
A:Basic, C:Plasma