4. Module Installation
4.1 Installation of Compressor Module
• You can install the compressor module directly on the floor or on a structure. If you want to install on floor, you
do not use ancor bolt.
• Install at places where it can endure the weight and vibration/noise of the compressor module.
• The compressor module supports at the bottom shall have width of at least 100mm under the Unit’s legs before
being fixed.
• The compressor module supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
Important
• For location of the Anchor bolts, refer to the dimensional drawings of each unit on Product data.
At least 100mm
At least 100mm
At least 100mm
For outdoor units
should not be
supported only
by the corner
supports.
Center of the Unit
At least 100mm
At least 100mm
At least 100mm