4. Module Installation
7
MULTI V
Modular Heat Pump
Installation Guide
̰
Foundation of Compressor Module
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation part
depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad shall be
more than 200mm).
WARNING
• Install where it can sufficiently support the weight of the outdoor unit.
If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the
water flowing out of the outdoor unit in operation), and the passages of the pipe and wiring, when making the
ground support.
CAUTION
• In case of on the floor you should not have to fix the
compressormodule with anchor bolts.
• In case of on the structure you can fix the Compressor module
securely use anchor bolts, nuts and washers to the
structure.The foundation must be larger than the image
• If noise / vibration occurs, install rubber pad under the product
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the compressor module before welding.
Not removing Pallet(Wood Support) causes hazard of fire
duringwelding.
• When vibration is transmitted to the building, use a
vibrationproof rubber (field supply).
Unit : mm
200
75
75
200
100
ⓐ
The corner part must be fixed firmly. Otherwise, the
support for the installation may be bent.
ⓑ
Get and use M10 Anchor bolt.
ⓒ
Put Cushion Pad between the outdoor unit and ground
support for the vibration protection in wide area.
ⓓ
Space for pipes and wiring (Pipes and wirings for bot-
tom side)
ⓔ
H-beam support
ⓕ
Concrete support
At least 200mm
ⓐ
ⓑ
ⓒ
ⓓ
ⓔ
ⓕ
Pallet(Wood Support)
- Remove before Installation
Summary of Contents for ARUN050GME0
Page 1: ...Modular Heat Pump R410A 50Hz 5CVD0 01A P No MFL67474053 ...
Page 2: ...MULTI V S Modular Heat Pump General information Product Data Installation Guide ...
Page 11: ...MULTI V Modular Heat Pump 3 Dimensions 6 Product Data GG B8 Chassis ARUN050GME0 ...
Page 27: ...22 MULTI V Modular Heat Pump Product Data 10 Wiring Diagrams ARUN050LMC0 ARUN050GME0 ...