Ceiling Concealed Duct
14
_ Inverter
50Hz/R410A
Part 3 Design and installation
n
Wide Wired Remote Controller
①
Zone type setting
It is possible to setup zone new type or old one of the product which is available to install the damper controller.
CAUTION
If you set zone number incorrectly, the product may malfunction especially in zone control.
This function must carried out by a certificated-technician.
Function Code
Zone type
value
Select Zone State rate fixing mode by
pressing button.
00:Zone Controller, 01:Damper Controller
3
Press button to save.
4
If pressing button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
1
If moving to ceiling height selection menu by
pressing button, it indicates as picture
below.
2
Pressing button will exit settings mode.
❈
After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈
When exiting without pressing set button,
the manipulated value is not reflected.
5
1. Installation