96
ENGLISH
NOTES
Object Property Table
The properties of each object are listed on the following table.
The gateway is divided into 3 types of properties like O, R, W.
O: Optional property
R: Essential attributes available to monitor
W: Essential attributes available to control and monitor
Analog Input Object Type
Property Identifier
Property Datatype
ACP BACnet
Object_Identifier BACnetObjectIdentifier
R
Object_Name CharacterString
R
Object_Type BACnetObjectType
R
Present_Value Real
R
Description CharacterString
R
Device_Type CharacterString
-
Status_Flags BACnetStatusFlags
R
Event_State BACnetEventState
R
Reliability BACnetReliability
R
Out_Of_Service BOOLEAN
R
Update_Interval Unsigned
-
Units BACnetEngineeringUnits R
Min_Pres_Value REAL
R
Max_Pres_Value REAL
R
Resolution REAL
R
COV_Increment REAL
R
Time_Delay Unsigned
-
Notification_Class Unsigned
-
High_Limit Real
-
Low_Limit Real
-
Deadband Real
-
Limit_Enable BACnetLimitEnable
-
Event_Enable BACnetEventTransitionBits
-