15

ENGLISH

INSTALLING ACP BACnet 

The following figure is an example of connecting several PI485 with each other to connect to one 

ACP BACnet.

10V

GND

BUS_A

BUS_B

10V

G

ND

BUS_A

BUS_B

10V

G

ND

BUS_A

BUS_B

PQNFB17C0 

BUS A

BUS B

Tape shield
back

Wire
Nut

Wire
Nut

Earth Ground

PQNFB17C0 

Summary of Contents for BECON HVAC BACnet PQNFB17C0

Page 1: ...talling the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly INSTALLATION OWNER S MANUAL AIR CONDITIONER P NO MFL68660306 www lg com ENGLISH ...

Page 2: ......

Page 3: ...sed under license from LG Electronics in strict adherence to the user agreement You may not reproduce or distribute by any means copies of this User Guide or any part of it without prior approval from LG Electronics Copyright 2014 LG Electronics All rights reserved Registered Trademarks ACP BACnet is a registered trademark of LG Electronics All other products and company names are trademarks of th...

Page 4: ... to cool or warm indoor air quickly in a short period of time Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours Clean the air filter once every 2 weeks Dust and impurities collected in the air filter may block the air flow or weaken the cooling dehumidifying functions Notes The product images and descriptions included in ...

Page 5: ... service technician familiar with safety procedures and equipped with the proper tools and test instruments y Failure to carefully read and follow all instructions in this manual can result in equipment malfunction property damage personal injury and or death Installation y Any question about the product installation should be asked to the service center or the professional installation agency It ...

Page 6: ...shock explosion or injury y Do not connetion 220 V power to 24 V products If you do not follow It may cause fire electric shock explosion or injury y Do not connect power cord to the control signal connector It may cause fire or explosion y Fix cables tightly when wiring power cord communication wires and etc Fire or electric shock accidents can occur if cables are loose y Prepare adequate protect...

Page 7: ...age temperature boundary in the manual If there is no specified tempera ture please use the product within the boundary of 0 40 C y Do not click the switch with wet hand It may cause electric shock or failure of the product y Please read installation and user manual for connection with PC or peripheral devices It may cause fire or failure of the product y If a warning window appears on PC product ...

Page 8: ...ured when using the product According to IEC 60335 1 This appliance is not intended for use by person including children with reduced physical or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the...

Page 9: ...ng the ACP BACnet installation 11 Setting the indoor unit address 14 Setting the PI485 and connecting the cable 16 Installing ACP BACnet and connecting cables 21 Setting the ACP BACnet network address 32 Setting the functions of the ACP BACnet 47 LG S ACP BACnet AGREEMENT 49 FUNCTIONAL SPECIFICATIONS ACP BACnet 84 NOTES 84 Troubleshooting 88 OPEN SOURCE SOFTWARE NOTICE 89 BIBBs 96 Object Property ...

Page 10: ...viii ENGLISH MEMO ...

Page 11: ...ns Major functions of the ACP BACnet are as follows Environment setting function using the ACP BACnet external buttons ACP BACnet can use the external buttons installed outside of the ACP BACnet to set the following functions Set Network environment IP address Net mask Gateway Set the function to use between Peak demand function SW upgrade function Data backup function Data recovery function RS 48...

Page 12: ... ACS I O Interlocking on version 4 0 0 or later Control up to 128 indoor units and 16 I O modules Monitoring of error and operation status Controlling the peak power demand power System setting function Devices that can interface with ACP BACnet Device ACP BACnet less than version 4 0 0 ACP BACnet version 4 0 0 or later AC Ez O O Simple Central Controller O O AC Smart O X AC Smart IV X O AC Manage...

Page 13: ...ompletely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly INSTALLATION OWNER S MANUAL AIR CONDITIONER P NO MFL68660306 www lg com ENGLISH ACP BACnet User Manual www lg com After reading this user manual keep it in an...

Page 14: ...4 ENGLISH ACP BACnet FUNCTIONS AND SPECIFICATION Names of each part of ACP BACnet ACP BACnet is composed as follows PQNFB17C0 PQNFB17C0 PQNFB17C0 PQNFB17 ª 7C0 Notes and may be different for each model ...

Page 15: ...ailable to connect external I O CH5 CH6 are Modbus Channels Not used in US RS 485 communication port RS 485 communication ports to connect to air conditioner and ERV equipment 4 in total Mini USB port USB to Serial port for software debugging USB port For software update and data backup Power switch Switch to turn on or off the power of the ACP BACnet Ethernet port Ethernet port to connect to inte...

Page 16: ...unication ports y Ethernet 10 100 BASE T y USB USB Host SW upgrade data backup mini USB Device Debug y RS 485 communication ports 6EA y SD card slot RS 485 communication logging External input output ports DI DO LED 27EA RS communication status Ethernet communication status power status operation status LCD 20 4 Character LCD network environment setting and information display Notes License policy...

Page 17: ...r unit address Do not duplicate IDU addresses STEP 4 Set PI485 and connect cables Set DIP switch of PI485 correctly and connect RS 485 communication cable STEP 5 Install ACP BACnet and connect cables Install the ACP BACnet and set network and other settings STEP 6 Set ACP BACnet network address Set the network address to be able to access the ACP BACnet Via local ethernet subnet STEP 7 Set ACP BAC...

Page 18: ... the ACP BACnet y The ACP BACnet installation should be performed by the certified installation professional y Consult the service center or the professional installation agency certified by us about any question or request related to the installation ...

Page 19: ...its With ACS I O interlocking you can connect 128 indoor units and 16 I O modules To one RS 485 port all of 256 indoor units which is the maximum number that can be connected to the ACP BACnet may be connected but communication latency will increase But to improve the communication performance of RS 485 it is recommended to be divided and connected to 4 ports The maximum quantity of connected indo...

Page 20: ...able exceed total of 1 km RS 485 communication cable must be connected with BUS type IP address of the ACP BACnet IP address of the ACP BACnet address of Gateway and Net mask must be requested to the person in charge of the network of the corresponding site Caution RS 485 Connection of the ERV equipment To connect ERV equipment it is recommended to use the ports other than RS 485 communication por...

Page 21: ...t address However in case of I O module address 00 should not be set because address 00 is used as Broadcast in MODBUS communication Notes Assigning indoor and outdoor unit number If the outdoor unit product is Multi V it is recommended to assign the address by setting the first digit of the address as the number of the outdoor unit and classifying the second digit as the number or the indoor unit...

Page 22: ...ribution Indicator PDI watt hour meter CH1 2 3 or 4 CH5 or CH6 ERV DI DO DOKIT AWHP AHU Not available in US Market Indoor devices 1 Configuration Address 01 Configuration Address 11 Configuration Address 21 Configuration Address 31 Configuration Address 41 Configuration Address 02 Configuration Address 03 Indoor devices 2 Indoor devices 3 ...

Page 23: ...0 or later the ERV can be installed together and controlled The above figure shows the example that sets the addresses of 11 to the ERV and connects to the ACP BACnet Notes How to set the central control address of the indoor unit Please refer to the individual remote controller manual for function address configuration ...

Page 24: ...5 by referring to the PI485 manual or the installation technique information To connect PI485 and the ACP BACnet two RS 485 cables need to be connected to BUS A and BUS B of PI485 Connect RS 485 cable by referring to the following figure XW nuk i z h i z i nu nu nu nu nu nu nu nu nu nu nu nu nu nu nu n n n n n n k i z h i z i i i i i i i i i i i i i i i i i i i i If several PI485 are connected to ...

Page 25: ...llowing figure is an example of connecting several PI485 with each other to connect to one ACP BACnet 10V GND BUS_A BUS_B 10V GND BUS_A BUS_B 10V GND BUS_A BUS_B PQNFB17C0 BUS A BUS B Tape shield back Wire Nut Wire Nut Earth Ground PQNFB17C0 ...

Page 26: ...able shall be connected for the communication with PI485 Ethernet cable LAN cable shall be connected for use with Local Area Network PC or AC Manager AC Manager IV on version 4 0 0 or later To fix the ACP BACnet the following 2 methods may be used Install in DIN RAIL or fix to the wall considering the environment of the site PQNFB17C0 Power LAN cable RS 485 cable ...

Page 27: ...net check if it is the adequate place to connect the ACP BACnet with the power RS 485 and LAN cable Install DIN RAIL Hook the top part of the ACP BACnet on DIN RAIL Push the main body of the ACP BACnet until you hear the sound of installation Pull the ACP BACnet to check if it is fixed Hooking on DIN RAIL Fixing to DIN RAIL Caution y After installing to DIN RAIL do not fix to the wall using screws...

Page 28: ... RS 485 cable to the ACP BACnet After securing ACP BACnet the RS 485 communications wiring should be terminated Connect the RS 485 cable to BUS A and BUS B terminals RS 485 cable that was connected to PI485 shall be connected to CH port RS 485 port of the ACP BACnet Plug the connector connecting RS 485 cable into one of CH1 CH4 ports There are 1 6 CH ports and it must be plugged into one of 1 4 po...

Page 29: ...ropriately connected to CH1 to CH4 in BUS format Otherwise the ACP BACnet may malfunction The following is an example of dividing to CH1 and CH2 and connecting in BUS format BUS A BUS B BUS B BUS A ACP BACnet PQNFB17C0 The next shows the wrong example STAR connection of RS 485 connection of the ACP BACnet PQNFB17C0 LON SVC N A BUS A BUS B ACP BACnet Caution If a different type of connection is mad...

Page 30: ...cted as a direct cable Use Ethernet cable direct cable to connect to LAN port of the ACP BACnet Connecting ACP BACnet and PC It is the case of installing AC Manager AC Manager IV on version 4 0 0 or later in a separate PC and connecting ACP BACnet and PC directly In such case Ethernet cable shall be connected as a cross cable Use Ethernet cable cross cable to connect to LAN port of the ACP BACnet ...

Page 31: ...ion Setting the network environment information Network environment settings must be entered correctly for proper operation Please double check settings after entering Before configuring the ACP BACnet environment The network environment of the ACP BACnet can be set by the LCD and the buttons at the front side of the ACP BACnet The current ACP BACnet information and the menu are displayed on the L...

Page 32: ...ACnet screen is displayed LG BACnet SW ver 1 0 0 IP 192 168 001 100 GW 192 168 001 001 LG Electronics Wait for booting Notes Hardware classification The ACP BACnet with the basic hardware is displayed as LG BACnet at the initial ACP BACnet screen The ACP BACnet with the advanced hardware is displayed as LG BACnet G at the initial ACP BACnet screen Also the hardware may be different according to th...

Page 33: ...ion The software version of the current ACP BACnet is displayed at the initial ACP BACnet screen Also the software version may be different according to the manufacturing date of the ACP BACnet LG BACnet SW ver 1 0 0 IP 192 168 001 100 GW 192 168 001 001 ...

Page 34: ...nu in the following figure In Contents menu you can set the functions of the ACP BACnet and select language to use When you select Function and press SET button it enters the No 3 menu in the following figure In Function menu ACP BACnet software service function is supported When you select Register FD and press SET button it enters the No 4 menu in the following figure For more information please...

Page 35: ...d in the initial screen of Network Info menu and RX FDQ FKHFN 0 DGGUHVV DQG 3 VHWWLQJ XVLQJ GRZQ ź EXWWRQ Network Info Network Info IP GW MS 000 000 000 000 000 000 000 000 000 000 000 000 MC 000000 00 00 00 DHCP NO DOWN UP To change the network setting locate the arrow on the corresponding setting position and press SET button to enter the corresponding setting screen Network Info IP GW MS 000 00...

Page 36: ...2 168 000 000 Set IP Address 192 167 000 000 Click GRZQ ź button DPSOH RI SUHVVLQJ ULJKW Ź EXWWRQ PQNFB17C0 PQNFB1 FB1 FB1 1 B1 FB1 NFB1 FB1 FB1 NFB1 B1 1 NFB NFB1 FB1 B1 B B B B1 1 FB1 F FB1 NF NF 1 F 7C0 7C 7 7 7C0 0 0 0 0 0 7C0 0 0 7 7 0 0 C0 7C0 0 0 0 0 0 C C0 C C C C Set IP Address 192 168 000 000 Set IP Address 192 168 000 000 Click ULJKW Ź button Caution Setting the network address y The ne...

Page 37: ...een to input IP address PQNFB17C0 PQNFB1 FB1 NFB1 NFB1 B1 1 FB1 FB1 1 NFB1 1 FB1 B1 1 FB1 FB1 NFB FB1 B FB1 FB FB B1 B B1 NFB1 1 FB1 F NF 17C0 7C 7C0 0 0 C0 0 7C0 7C0 C0 0 0 0 0 0 0 C0 0 C0 C0 0 C C C C Network Info IP GW MS 000 000 000 000 000 000 000 000 000 000 000 000 Set IP Address 000 000 000 000 Network Info Contents Function Register FD Click SET button Click SET button 2 8VH XS GRZQ OHIW ...

Page 38: ...FB1 B1 1 FB1 FB1 B1 NFB1 1 NFB1 FB1 1 FB1 B1 FB1 B1 FB1 B FB1 FB B1 B B NFB1 FB1 F NFB1 F FB N C0 C0 0 7C0 C0 7C0 0 0 0 0 0 0 0 0 C C0 0 C C C C C C C C Network Info MC DHCP NO 000 000 000 000 Set DHCP NOT 0 USE 1 0 Network Info Contents Function Register FD Click SET button OLFN ź button four times Click SET button 2 8VH XS DQG GRZQ Ÿ ź EXWWRQV WR VHW ZKHWKHU WR XVH 3 IXQFWLRQ KHQ RX SUHVV XS Ÿ E...

Page 39: ...29 ENGLISH INSTALLING ACP BACnet Caution y The DHCP assigned IP address can be read in the front LCD y If you input the ACP BACnet IP address in the web browser you can run the ACP BACnet program again ...

Page 40: ...erly done You can check the possibility of accessing the ACP BACnet through PING test 1 You can open the following DOS window through Windows Start Run cmd input 2 In DOS screen input ping ACP BACnet IP address as follows to run PING test When the network setting is properly done When the network setting is not properly done ...

Page 41: ...55 255 0 y Check the status of the Ethernet cable LAN cable When PC and ACP BACnet are connected together in a hub or a switch hub and you cannot access the ACP BACnet y If it is right after changing the IP setting of the ACP BACnet reset the power of the ACP BACnet y If it is right after connecting LAN cable to the hub or switch it may take time for the hub or the switch to recognize the ACP BACn...

Page 42: ...es can be effectively saved The ACP BACnet offers two functions to limit the maximum power consumption of the air conditioner as follows Peak The maximum power consumption of the air conditioner can be managed by setting the maximum usage operation ratio in the ACP BACnet Demand Not used One of these two methods can be selected and used in the ACP BACnet And if it is set by the menu of the ACP BAC...

Page 43: ... C0 0 C0 7C0 7C0 C0 C0 7C0 0 0 7C0 7C0 0 0 0 0 0 C0 0 C C C C C C Network Info Contents Function Register FD Set PeakDemand PK 0 DMD 1 0 Contents 1 2 Peak Demand ACP ID Fahrenheit 0 0 0 Click SET button Click SET button 2 8VH XS DQG GRZQ Ÿ ź EXWWRQV WR VHW WKH GHVLUHG SRZHU PDQDJHPHQW PHWKRG I RX SUHVV XS Ÿ EXWWRQ LW LV VHW WR GHPDQG PHWKRG DQG LI RX SUHVV GRZQ ź EXWWRQ LW LV VHW WR SHDN PHWKRG PQ...

Page 44: ... setting function To send the Celsius temperature to the BMS set Fahrenheit to 0 To send the Fahrenheit temperature to the BMS set Fahrenheit to 1 Proceed in the following order 1 When you press SET EXWWRQ PHQX VFUHHQ ZLOO EH GLVSOD HG 8VH XS DQG GRZQ Ÿ ź EXWWRQV of the ACP BACnet to select Contents and press SET button again While Fahrenheit is selected pressing SET button will display the screen...

Page 45: ...order 1 When you press SET EXWWRQ PHQX VFUHHQ ZLOO EH GLVSOD HG 8VH XS DQG GRZQ Ÿ ź EXWWRQV of the ACP BACnet to select Contents and press SET button again While Device ID is selected pressing SET button will display the screen to select Device ID PQNFB17C0 PQNFB1 B1 NFB1 1 1 1 B1 1 B1 FB1 FB1 NFB1 FB1 1 B NFB1 FB1 NFB1 FB B FB B NFB1 F FB1 FB1 B B B1 FB FB F 1 N 7 7C0 0 0 C0 C0 0 7C0 0 0 C0 0 0 0...

Page 46: ...set Vnet Number PQNFB17C0 PQNFB1 FB1 NFB1 NFB1 B1 1 FB1 FB1 B1 NFB1 1 NFB1 1 FB1 FB1 FB1 FB FB1 FB FB B1 B B1 NFB1 1 FB1 F NF 17C0 7C0 7C 7C0 0 C0 0 7C0 7C0 C0 0 0 0 0 0 C0 0 C0 C0 0 C C C C C Contents 2 2 Device ID 9000 Vnet No 10 Network Info Contents Function Register FD Set VNET NO 000010 Click SET button Click SET button Software service function The following software service function can be...

Page 47: ...he specialized service technician Software update can be done with USB memory Proceed in the following order 1 Create ramdisk folder in USB memory 2 3XW WKH 6 ILOH WR XSGDWH LQ ƍUDPGLVNƍ IROGHU At this time only one S W file must be put New version software file can be downloaded from LG Electronics System Air Conditioner homepage ...

Page 48: ...38 ENGLISH INSTALLING ACP BACnet E may be changed ...

Page 49: ...Cnet in the future PQNFB17C0 PQNFB1 NFB1 B1 FB1 1 NFB1 1 NFB1 NFB1 FB1 B1 NFB1 FB1 FB1 NFB NFB1 B1 B B1 FB B1 B B1 B B FB1 1 NFB1 F 1 B FB 7C 7 7 7C0 0 0 C0 0 0 C0 0 C0 7C0 0 0 0 0 0 0 0 0 C0 C0 C0 C C C C Network Info Contents Function Register FD Function 1 2 S W update DB back up DB recover S W update SET Yes ESC No Completed Restart now SET Yes ESC No Please wait Click SET button Click SET but...

Page 50: ... backup is necessary it must be carried out by the specialized service technician Data backup can be done with USB memory or SD card Proceed in the following or der 1 Insert USB memory or SD card into the ACP BACnet Refer to software update for USB memory insertion ...

Page 51: ...1 1 FB1 FB1 NFB1 NFB1 1 B FB1 FB1 FB1 FB B FB B NFB1 FB1 1 NFB1 F FB1 FB F N 7 7C0 0 0 C0 C0 0 7C 7C0 0 0 0 0 0 0 C0 0 0 0 C0 C0 C C C C C Network Info Contents Function Register FD DB back up USB SD card Function 1 2 S W update DB back up DB recover Completed Remove USB or SD card Click SET button Click SET button Click SET button Remove USB memory or SD card Caution Before data backup is complet...

Page 52: ... recovery is necessary it must be carried out by the specialized service technician Data recovery can be done with USB memory or SD card Proceed in the following order 1 Save the database file to recover in USB memory or SD card Save the files in db folder as follows ...

Page 53: ...estarted for data recovery PQNFB17C0 PQNFB1 B1 NFB1 1 1 1 B1 1 B1 FB1 FB1 NFB1 FB1 1 B NFB1 FB1 NFB1 FB B FB B NFB1 F FB1 FB1 B B B1 FB FB F 1 N C0 0 C0 0 7C0 C0 C0 0 7C0 0 7C0 0 C0 0 0 0 0 C0 C C C C C Network Info Contents Function Register FD DB recover USB SD card Function 1 2 S W update DB back up DB recover Completed Remove USB or SD card Completed Auto Restart Click SET button Click SET but...

Page 54: ... BACnet 3 Select Function menu and press SET button 4 Select Data Logging menu and press SET button again 5 Select whether to set data logging PQNFB17C0 PQNFB1 NFB1 NFB1 B1 1 FB1 FB1 B1 NFB1 1 NFB1 FB1 1 FB1 B1 FB1 B1 FB1 B FB1 FB B1 B B NFB1 FB1 F NFB1 F FB N 7 7C0 C0 C0 C0 0 0 0 0 0 0 0 C0 0 0 C C0 0 C C C C C C C C Network Info Contents Function Register FD Data Logging Function 1 2 Function 2 ...

Page 55: ...ng PQNFB17C0 PQNFB1 NFB1 NFB1 B1 1 FB1 FB1 1 NFB1 1 NFB1 FB1 1 FB1 B1 FB1 B1 FB1 B FB1 FB B1 FB B NFB1 B FB1 NFB1 F FB N 7C0 7C0 7C0 7C0 7C0 C0 C0 7C0 0 0 0 0 0 0 C0 0 0 C C C C C C C C Network Info Contents Function Register FD Set FD IP 192 168 000 000 IP 000 000 000 000 PORT 00000 TTL 00000 ON 0 Click SET button Click SET button Example of PORT setting PQNFB17C0 PQNFB1 NFB1 1 NFB1 FB1 B1 NFB1 1...

Page 56: ...00 000 000 PORT 00000 TTL 00000 ON 0 Click SET button Click SET button Example of Foreign Device Activate setting PQNFB17C0 PQNFB1 NFB1 NFB1 B1 1 FB1 FB1 B1 NFB1 1 NFB1 FB1 1 FB1 FB1 FB1 FB FB1 FB B B1 B B1 NFB1 FB1 F NFB1 FB1 N 7 7C0 C0 C0 C0 0 0 0 0 0 0 0 C0 0 C0 C C0 0 C C C C C C C Network Info Contents Function Register FD Set FD ACTIVATE NOT 0 USE 1 0 IP 000 000 000 000 PORT 00000 TTL 00000 ...

Page 57: ... s prior to connection with the BMS system BMS Engineering Creating of the Points This is NOT to be done by LG since it is directly related to the BMS side The BMS engineer is to carry out the engineering of the Point however LG is responsible for providing the method of how the Points are calculated Commission First step only using LG s ACP BACnet without connecting BMS This is to be carried out ...

Page 58: ...s After the LG s ACP BACnet agreement part please consult with the experts of BMS PQNFB17C Hub BACnet LG NET ACP BACnet Diagnosis 1 Creating of indoor and vent points 2 Test of all units and operations BMS Engineering Side LG Engineering Side ...

Page 59: ...ormation of A C vent that are connected to the ACP BACnet s internal LG NET will be sent in BACnet service form and BACnet client provides a function that transmits control command to the A C vent system Configuration of Connection A BACnet client that supports BACnet ANSI ASHRAE135 protocol allows direct connection via generally used HUBs or Ethernet The image of its connection configuration is a...

Page 60: ...tting LockCommand_XXX BO Permit Prohibit 4 Lock Status LockStatus_XXX BI Permit Prohibit 5 Filter Sign Filter Sign_XXX BI Off On 6 Filter Sign Reset Filter Sign Reset_XXX BV Reset 7 Operation Mode Setting ModeCommand_XXX MO Cool Dry Fan Auto Heat 8 Operation Mode Status ModeStatus_XXX MI Cool Dry Fan Auto Heat 9 Swing Setting SwingCommand_ XXX BO Stop Run 10 Swing Status SwingStatus_XXX BI Stop Ru...

Page 61: ...werStatus_ XXX AI Wattage values Unit 100Watt 27 Set Upper Temperature Set ting SetUpperTempCom mand_XXX AV C 28 Set Lower Temperature Set ting SetLowerTempCom mand_XXX AI C 29 Set Upper Temperature Sta tus SetUpperTempSta tus_XXX AI C 30 Set Lower Temperature Sta tus SetLowerTempSta tus_XXX AI C 31 Mode Lock Setting ModeLockCommand_ XXX BO Permit Prohibit 32 Mode Lock Status ModeLockStatus_ XXX B...

Page 62: ... Setting 2SetCoolingUpperLimitCommand_XXX AV C 42 2Set Cooling Upper Temperature Status 2SetCoolingUpperLimitStatus_XXX AI C 43 2Set Heating Upper Temperature Setting 2SetHeatingUpperLimitCommand_XXX AV C 44 2Set Heating Upper Temperature Status 2SetHeatingUpperLimitStatus_XXX AI C 45 2Set Cooling Lower Temperature Setting 2SetCoolingLowerLimitCommand_XXX AV C 46 2Set Cooling Lower Temperature Sta...

Page 63: ...2 1 The indoor unit will disregard the command which the object which can t select the operation mode Therefore controlled monitored system shouldn t use the object which can t select the operation mode 3RLQW 12 1 Present_value property will be set to 1 Low as the default result if the property has not been set in the past 3RLQW 12 1 The approximate set temperature range is 18 35 C 2 When COV regi...

Page 64: ... StartStopStatus_XXX BI Stop Run 3 Lock Setting LockCommand_XXX BO Permit Prohibit 4 Lock Status LockStatus_XXX BI Permit Prohibit 5 Filter Sign Filter Sign_XXX BI Off On 6 Filter Sign Reset Filter Sign Reset_XXX BV Reset 7 Operation Mode Setting ModeCommand_XXX MO Heat Exchange Auto Normal 8 Operation Mode Status ModeStatus_XXX MI Heat Exchange Auto Normal 9 10 11 Fan Speed Setting FanSpeedComman...

Page 65: ...aving Clear 18 User Mode Status UserModeStatus_ XXX MI Quick Fresh Energy Saving Clear 19 C 20 Power Distribution AccumPowerStatus_ XXX AI Wattage values Unit 100Watt 21 AC Operation Mode set ting HrvModeCommand_ XXX MO Cool Auto Heat 22 AC Operation Mode status HrvModeStatus_XXX MI Cool Auto Heat 23 AC ON OFF setting HrvStartStopCom mand_XXX BO Stop Run 24 AC ON OFF status HrvStartStopStatus_ XXX...

Page 66: ...nges the corresponding Event will be transmitted if the Event has been registered 3RLQW 12 1 The Present_Value property will be set to 1 Cool as the default value if property has never been set in the past 2 The vent will ignore the command to an object that does not have right to select operation mode Therefore the controlled monitored system must not use this object for the vent without the righ...

Page 67: ...X BI Stop Run 3 Lock Setting LockCommand_XXX BO Permit Prohibit 4 Lock Status LockStatus_XXX BI Permit Prohibit 5 Filter Sign Filter Sign_XXX BI Off On 6 Filter Sign Reset Filter Sign Reset_XXX BV Reset 7 Operation Mode Setting ModeCommand_XXX MO Cool Dry Fan Heat 8 Operation Mode Status ModeStatus_XXX MI Cool Dry Fan Heat 9 10 11 12 13 Set Room Tempe rature SetRoomTemp_XXX AV C 14 Room Temperatu ...

Page 68: ...HumidifyStatus_XXX BI Stop Run 26 Auto Ventilation Setting AutoVentilCommand_XXX BO Stop Run 27 Auto Ventilation Status AutoVentilStatus_XXX BI Stop Run 28 Supply Temperature Status SupplyTempStatus_XXX AI 127 127 29 Outdoor Temperature Status OutdoorTempStatus_XXX AI 127 127 30 Mix Temperature Status MixTempStatus_XXX AI 127 127 31 Supply Humidity Status SuppyHumidifyStatus_XXX AI 30 90 32 Outdoo...

Page 69: ..._XXX AI 0 90 40 Current EA Dam per Status CurEADamperStatus_XXX AI 0 90 41 Current MIX Dam per Status CurMixDamperStatus_XXX AI 0 90 42 Cool OA Damper Setting OADamperCoolCommand_ XXX AV 0 90 43 Cool OA Damper Status OADamperCoolStatus_XXX AI 0 90 44 Cool EA Damper Setting EADamperCoolCommand_ XXX AV 0 90 45 Cool EA Damper Status EADamperCoolStatus_XXX AI 0 90 46 Cool MIX Damper Setting MixDamperC...

Page 70: ... EA Damper Status EADamperHeatStatus_XXX AI 0 90 52 Heat MIX Damper Setting MixDamperHeatCommand_ XXX AV 0 90 53 Heat MIX Damper Status MixDamperHeatStatus_XXX AI 0 90 54 Fan OA Damper Setting OADamperFANCommand_ XXX AV 0 90 55 Fan OA Damper Status OADamperFANStatus_XXX AI 0 90 56 Fan EA Damper Setting EADamperFANCommand_ XXX AV 0 90 57 Fan EA Damper Status EADamperFANStatus_XXX AI 0 90 58 Fan MIX...

Page 71: ...d even if INACTIVE is written 3 This object supports the Intrinsic Reporting function When the Present_Value property changes the corresponding Event will be transmitted if the Event has been registered 3RLQW 12 1 The Present_Value property will be set to 1 Cool as the default value if property has never been set in the past 2 AHU will ignore the command to an object that does not have right to se...

Page 72: ...ext 2 Text 3 Text 4 Text 5 1 Compressor Operation Sta tus C o m p O p e r S t a t u s _ XXX BI Stop Run 2 Refrigent Type RefrigentType_XXX MI R407C 5 3 Inverter Fan 1 frequency InverterFanFreq_XXX AI 4 High Pressure HighPressure_XXX AI 5 Low Pressure LowPressure_XXX AI 6 Sunction Temperature SunctionTemp_XXX AI Ȕ 7 Liquid Pipe Temperature LiquidPipeTemp_XXX AI Ȕ 8 Heat Exchanger Tempera ture HexTe...

Page 73: ...d_XXX BO Stop Run 4 Lock status LockStatus_XXX BI Stop Run 5 Operation Mode setting ModeCommand_XXX MO Cool Heat Auto 6 Operation Mode status ModeStatus_XXX MI Cool Heat Auto 7 Set Room Temperature set ting SetRoomTempCommand_ XXX AO 8 Set Room Temperature sta tus SetRoomTempStatus_XXX AI 9 Set Hot Water Temperature setting SetHotWaterTempCom mand_XXX AO 10 Set Hot Water Temperature status SetHotW...

Page 74: ...Temperature RoomTemp_XXX AI 16 Alarm Event Alarm_XXX BI No error Error 17 Malfunction Code MalfunctionCode_XXX AI Reference LG Original Error Code 18 HotWater On Off setting HotWaterCommand_XXX BO 19 HotWater On Off status HotWaterStatus_XXX BI 20 Pipe Inlet Temperature Sta tus PipeInTempStatus_XXX AI 21 Water Tank Temperature Status TankTempStatus_XXX AI 22 Solar Temperature Status SolarTempStatu...

Page 75: ...Command AV C 3 All Unit Temperature Lock Set ting AllTempLockCommand AV C 4 Total Accumulated Power Status TotalAccumulatedPower AI 5 Peak Control Operation Setting PeakStartStopCommand BO Stop Run 6 Peak Control Operation Status PeakStartStopStatus BI Stop Run 7 Peak Shift Time Setting PeakShiftTimeCommand AV Minute 8 Peak Shift Time Status PeakShiftTimeStatus AI Minute 9 Peak Target Ratio Settin...

Page 76: ...o BMS and BMS registers the object Case Indoor Address Product Type Product No Point No Instance No Name 0 0 0 1 0x00001 1 ON OFF setting 0 0 0 2 0x00002 2 ON OFF status 1 0 1 1 0x00101 257 ON OFF setting 1 0 1 2 0x00102 258 ON OFF status 15 0 15 1 0x00F01 3841 ON OFF setting 15 0 15 2 0x00F02 3842 ON OFF status 16 0 16 1 0x01001 4097 ON OFF setting 16 0 16 2 0x01002 4098 ON OFF status 255 0 255 1...

Page 77: ...ting 15 1 15 2 0x10F02 69378 ON OFF status 16 1 16 1 0x11001 69633 ON OFF setting 16 1 16 2 0x11002 69634 ON OFF status 255 1 255 1 0x1FF01 130817 ON OFF setting 255 1 255 2 0x1FF02 130818 ON OFF status Case AHU Address Product Type Product No Point No Instance No Name 0 2 0 1 0x20001 131073 ON OFF setting 0 2 0 2 0x20002 131074 ON OFF status 1 2 1 1 0x20101 131329 ON OFF setting 1 2 1 2 0x20102 1...

Page 78: ...89 Comp ON OFF status 255 3 255 2 0x3FF02 261890 Refrigent Type status Case AWHP Address Product Type Product No Point No Instance No Name 0 4 0 1 0x40001 262145 ON OFF setting 0 4 0 2 0x40002 262146 ON OFF status 1 4 1 1 0x40101 262401 ON OFF setting 1 4 1 2 0x40102 262402 ON OFF status 15 4 15 1 0x40F01 265985 ON OFF setting 15 4 15 2 0x40F02 265986 ON OFF status 16 4 16 1 0x41001 266241 ON OFF ...

Page 79: ...s Mode Lock status Wind Flow Lock status Read Holding Registers 03h Operation Mode status Fan Speed status Room Temperature Error Code Set Room Temperature status Set Lower Temperature status Set Upper Temperature status User Mode status Write Single Coil 05h Run Stop setting Lock setting Swing setting Filter Sign Reset Mode Lock setting Wind Flow Lock setting Write Single Registers 06h Operation ...

Page 80: ...atus_XXX Permit Prohibit 4 MODE LOCK ModeLockStatus_XXX Permit Prohibit 5 FAN LOCK WindFlowLockStatus_XXX Permit Prohibit 6 TEMP LOCK SetTempStatus XXX Permit Prohibit 7 ALARM Alarm_XXX Normal Abnormal 1 Write Single Coil ON OFF StartStopCommand_XXX Stop Run 2 SWING SwingCommand_XXX Permit Prohibit 3 LOCK LockCommand_XXX Permit Prohibit 4 MODE LOCK ModeLockCommand_XXX Permit Prohibit 5 FAN LOCK Wi...

Page 81: ... High Auto 3 SET ROOM TEM PERATURE SetTempStatus_XXX C 4 UP_SETTEMP SetUpperTemp Status_XXX C 5 LO_SETTEMP SetLowerTemp Status_XXX C 6 ROOM TEMPERA TURE RoomTemp_XXX C 7 ERROR CODE MalfunctionCode_XXX Reference LG original Error Code 1 Write Single Registers OPERATION MODE ModeCommand_XXX Cool Dry Fan Auto Heat 2 FAN SPEED FanSpeed Command_XXX Low Middle High Auto 3 SET ROOM TEM PERATURE SetTemp C...

Page 82: ...RGHB 1 This object s error code descriptions should be referred to the corresponding table at the Reference LG original Error Code 0RGH RPPDQGB 1 The Present_Value property will be set to 1 Cool as the default value if property has never been set in the past 2 The indoor unit will ignore the command to an object that does not have right to select operation mode Therefore the controlled monitored s...

Page 83: ...OCK LockStatus_XXX Permit Prohibit 3 FILTER SIGN FilterSign_XXX Off On 4 ALARM Alarm_XXX Stop Run 5 HRV_AC_OPER HrvStartStopStatus_XXX Stop Run 6 HRV_HUMIDIFY HrvHumidifyStatus_XXX Off On 1 Write Single Coil ON OFF StartStopCommand_XXX Stop Run 2 LOCK LockCommand_XXX Permit Prohibit 3 FILTER SIGN RESET FilterSignReset_XXX Reset Off Void On 5 HRV_AC_OPER HrvStartStopCommand_XXX Stop Run 6 HRV_HUMID...

Page 84: ... Auto 3 USER MODE UserModeStatus_XXX Quick Operation Energy Saving Heat 4 ERROR CODE MalfunctionCode_XXX Reference LG original Error Code 5 HRV_AC_MODE HrvModeStatus_XXX Cool Auto Heat 6 HRV_SETTEMP HrvSetTempstatus_XXX C 1 Write Single Registers OPERATION MODE ModeCommand_XXX Heat Exchange Auto Nor mal 2 FAN SPEED FanSpeed Command_XXX Low High Su per High Auto 3 USER MODE UserModeStatus_XXX Quick...

Page 85: ...me value as the Filter Limit Sign object 2 Only if ACTIVE is written to the Present_Value property during a write operation the filter sign information resets ON signs and nothing will be executed even if INACTIVE is written 3 This object supports the Intrinsic Reporting function When the Present_Value property changes the corresponding Event will be transmitted if the Event has been registered DQ...

Page 86: ...us_XXX Stop Run 5 HUMIDITY HumidifyStatus_XXX Stop Run 6 AUTO VENT AutoVentStatus_XXX Stop Run 7 HUMIDIFIER HumidifiyUnitStatus XXX Stop Run 8 HEATER HeaterUnitStatus_XXX Stop Run 9 VENT FAN VentFANStatus_XXX Stop Run 10 SUPPLY FAN SupplyFANStatus_XXX Stop Run 11 ALARM Alarm_XXX Normal Abnormal 1 Write Single Coil ON OFF StartStopCommand_XXX Stop Run 2 LOCK LockCommand_XXX Permit Prohibit 4 SMOKE ...

Page 87: ... 60 8 SUPPLY HUMIDITY SupplyHumidityStatus_XXX 30 90 9 OUTDOOR HUMIDITY OutdoorHumidityStatus_XXX 30 90 10 VENT HUMIDITY VentHumidityStatus_XXX 30 90 11 CO2 VALUE CO 2 ValueStatus_XXX 0 255 12 ERROR CODE MalfunctionCode_XXX Reference LG original Error Code 17 CURR_OA_DAMPER CurOADamperStatus_XXX 0 90 18 CURR_EA_DAMPER CurEADamperStatus_XXX 0 90 19 CURR_MIX_DAMPER CurMixDamperStatus_XXX 0 90 20 COO...

Page 88: ...s MODE ModeCommand_XXX Cool Dry Fan POWS AV Heat 2 SET TEMP SetTempCommand_XXX C 7 SET HUMIDITY SetHumidityCommand_XXX 40 60 20 COOL_OA_DAMPER CoolOADamperCommand_XXX 0 90 21 COOL_EA_DAMPER CoolEADamperCommand_XXX 0 90 22 COOL_MIX_DAMPER CoolMixDamperCommand_XXX 0 90 23 HEAT_OA_DAMPER HeatOADamperCommand_XXX 0 90 24 HEAT_EA_DAMPER HeatEADamperCommand_XXX 0 90 25 HEAT_MIX_DAMPER HeatMixDamperComman...

Page 89: ...property will not be used if a property has never been set in the past 0DOIXQFWLRQ RGHB 1 This object s error code descriptions should be referred to the corresponding table at the Reference LG original Error Code 0RGH RPPDQGB 1 The Present_Value property will be set to 1 Cool as the default value if property has never been set in the past 2 AHU will ignore the command to an object that does not h...

Page 90: ...ect Case Indoor Function Code Product Type Product No Point No Instance No Name 1 0 0 0 0x00000 ON OFF status 5 0 0 0 0x00000 ON OFF setting 1 0 1 0 0x00010 ON OFF status 5 0 1 0 0x00010 ON OFF setting 1 0 255 0 0x00FF0 ON OFF status 5 0 255 0 0x00FF0 ON OFF setting 3 0 0 0 0x40000 Mode status 6 0 0 0 0x40000 Mode setting 3 0 1 0 0x40010 Mode status 6 0 1 0 0x40010 Mode setting 3 0 255 0 0x40FF0 M...

Page 91: ...e setting 3 4 1 0 0x44010 Mode status 6 4 1 0 0x44010 Mode setting 3 4 255 0 0x44FF0 Mode status 6 4 255 0 0x44FF0 Mode setting Case AHU Function Code Product Type Product No Point No Instance No Name 1 8 0 0 0x08000 ON OFF status 5 8 0 0 0x08000 ON OFF setting 1 8 1 0 0x08010 ON OFF status 5 8 1 0 0x08010 ON OFF setting 1 8 15 0 0x080F0 ON OFF status 5 8 15 0 0x080F0 ON OFF setting 3 8 0 0 0x4800...

Page 92: ...tioner is accessed ErrorClass Object ErrorCode Unknown_Object If an attempt is made to read the Object List property of the Device object from an air conditioner during the above period of recognition the following error PDU will be returned unless the air conditioner has been recognize ErrorClass Device ErrorCode Configuration_In_Progress Communication error response of ACP BACnet please refer to...

Page 93: ...Value Notification A request for COV registration is accepted through the SubscribeCOV service 1 Setting of Confirmed or Unconfirmed COV This item is supported according to the BACnet Specifications 2 Setting of the desired lifetime of the subscription This item is supported according to the BACnet Specifications When COV notification is made at the time of status change the difference between the...

Page 94: ...ring the product installation run it after setting the indoor and outdoor unit groups When GUI cannot be operated in Web GUI which is the operation program of the ACP BACnet 1 When GUI cannot be operated in Web GUI which is the operation program of the ACP BACnet close Explorer window and run new Explorer to access again 2 Close all iexplorer exe process in Task Manager and access to the ACP BACne...

Page 95: ...242 network error keeps occurring and disappearing in the ACP BACnet controller Case of incorrect connection of RS 485 communication line If each communication line is connected altogether as in the following figure the communication line must be separated PI485 vu sXGGGYGGGZGGGG rzkv o PI485 vu sXGGGYGGGZGGGG rzkv o PI485 vu sXGGGYGGGZGGGG rzkv o PI485 vu sXGGGYGGGZGGGG rzkv o PQNFB17C0 LON SVC N...

Page 96: ...If the indoor unit to control with simple central controller is in another physical line as in the following figure the simple central controller cannot recognize the corresponding indoor unit Therefore the connections need to be modified to have the simple central controller to be in the same RS 485 communication line with the indoor unit to control 1 vu sXGGGYGGGZGGGG rzkv o 10 vu sXGGGYGGGZGGGG...

Page 97: ...nection status of the communication line Normal communication line connection Wrong connection When the image ofWeb GUI is broken and you cannot see the screen such as the temperature well 1 Close Web GUI and rerun Caution y If PC is used for a long period of time or several application programs are used at the same time PC performance may be degraded and may affect the ACP BACnet UI y When you us...

Page 98: ...ource code all referred license terms warranty disclaimers and copyright notices are available for download LG Electronics will also provide open source code to you on CD ROM for a charge covering the cost of performing such distribution such as the cost of media shipping and handling upon email request to opensource lge com This offer is valid for three 3 years from the date on which you purchase...

Page 99: ...ReadPropertyMultiple DS RPC A Data Sharing ReadProper tyConditiona A Ƒ ReadPropertyConditional DS RPC B Data Sharing ReadProper tyConditiona B Ƒ ReadPropertyConditional DS WP A Data Sharing WriteProperty A Ƒ WriteProperty DS WP B Data Sharing WriteProperty B Ŷ WriteProperty DS WPM A Sharing WritePropertyMultiple A Ƒ WritePropertyMultiple DS WPM B Data Sharing WriteProperty Multiple B Ŷ WriteProper...

Page 100: ...ubscribeCOV Confirmed COVNotification Unconfirmed COVNotification DS COVP B Data Sharing COVP B Ƒ SubscribeCOV Confirmed COVNotification Unconfirmed COVNotification DS COVU A Data Sharing COV Unsolici ted A Ƒ Unconfirmed COVNotification DS COVU B Data Sharing COV Unsolici ted B Ƒ Unconfirmed COVNotification ...

Page 101: ...d EventNotification Unconfirmed EventNotification AE ACK A Alarm and Event ACK A Ƒ AcknowledgeAlarm AE ACK B Alarm and Event ACK B Ƒ AcknowledgeAlarm AE ASUM A Alarm and Event Summary A Ƒ GetAlarmSummary AE ASUM B Alarm and Event Summary B Ƒ GetAlarmSummary AE ESUM A Event Summary A Ƒ GetEnrollment Summary AE ESUM B Event Summary B Ƒ GetEnrollment Summary AE INFO A Alarm and Event Information A Ƒ ...

Page 102: ... B shall support SCHED I B and DS WP A Ƒ Trending BIBBS Ƒ 1RW VXSSRUWHG Ŷ 6XSSRUW BIBB Type Supported ACP BACnet Service Initiate Execute T VMT A Trending Viewing and Modi fying Trends A Ƒ ReadRange T VMT I B Trending Viewing and Modi fying Trends Internal B Ƒ ReadRange T VMT E B Trending Viewing and Modi fying Trends External B Ƒ ReadRange T ATR A Trending Automated Trend Retrieval A Ƒ ConfirmedE...

Page 103: ...DeviceCommunica tion Control DM DCC B Device Management Device Communication Control B Ƒ DeviceCommunica tion Control DM PT A Device Management Private Transfer A Ƒ ConfirmedPrivate Transfer UnconfirmedPrivate Transfer DM PT B Device Management Private Transfer B Ƒ ConfirmedPrivate Transfer UnconfirmedPrivate Transfer DM TM A Device Management Text Message A Ƒ ConfirmedPrivate Transfer Unconfirmed...

Page 104: ...d Restore A Ƒ AtomicReadFile AtomicWriteFile CreateObject ReinitializeDevice DM BR B Device Management Backup and Restore B Ƒ AtomicReadFile DMAtomicWriteFile ReinitializeDevice DM R A Device Management Restart A Ƒ Unconfimed COVNotification DM R B Device Management Restart B Ƒ Unconfimed COVNotification DM LM A Device Management List Manipulation A Ƒ AddListElement RemoveListElement DM LM B Devic...

Page 105: ...h Connec tion To Network Disconnect Connec tion To Network NM CE B Network Management Con nection Establishment B Ƒ Establish Connec tion To Network Disconnect Connec tion To Network DM BR A Network Management Router Configuration A Ƒ Who Is Router To Network I Am Router To Network I Could Be Router To Network Initialize Routing Table Initialize Routing Table Ack NM RC B Network Management Router ...

Page 106: ...tObjectIdentifier R Object_Name CharacterString R Object_Type BACnetObjectType R Present_Value Real R Description CharacterString R Device_Type CharacterString Status_Flags BACnetStatusFlags R Event_State BACnetEventState R Reliability BACnetReliability R Out_Of_Service BOOLEAN R Update_Interval Unsigned Units BACnetEngineeringUnits R Min_Pres_Value REAL R Max_Pres_Value REAL R Resolution REAL R C...

Page 107: ...ctType R Present_Value Real W Description CharacterString R Status_Flags BACnetStatusFlags R Event_State BACnetEventState R Reliability BACnetReliability R Out_Of_Service Boolean R Units BACnetEngineeringUnits R PriorityArray BACnetPriorityArray R RelinquishDefault Real R COV_Increment Real R Time_Delay Unsigned Notification_Class Unsigned High_Limit REAL Low_Limit REAL Deadband REAL Limit_Enable ...

Page 108: ...BACnetEventState R Reliability BACnetReliability R Out_Of_Service Boolean R Polarity BACnetPolarity R Inactive_Text CharacterString R Active_Text CharacterString R Change_Of_State_Time BACnetDateTime Change_Of_State_Count Unsigned Time_Of_State_Count_Reset BACnetDateTime Elapsed_Active_Time Unsigned32 Time_Of_Active_Time_Reset BACnetDateTime Time_Delay Unsigned Notification_Class Unsigned Alarm_Va...

Page 109: ...ean R Polarity BACnetPolarity R Inactive_Text CharacterString R Active_Text CharacterString R Change_Of_State_Time BACnetDateTime Elapsed_Active_Time Unsigned32 Time_Of_Active_Time_Reset BACnetDateTime Minimum_Off_Time Unsigned32 Minimum_On_Time Unsigned32 Priority_Array BACnetPriorityArray R Relinquish_Default BACnetBinaryPV R Time_Delay Unsigned Notification_Class Unsigned Feedback_Value BACnetB...

Page 110: ...R Active_Text CharacterString R Change_Of_State_Time BACnetDateTime Chgange_Of_State_Count Unsigned Time_Of_State_Count_Reset BACnetDateTime Elapsed_Active_Time Unsigned32 Time_Of_Active_Time_Reset BACnetDateTime Minimum_Off_Time Unsigned32 Minimum_On_Time Unsigned32 Priority_Array BACnetPriorityArray R Relinquish_Default BACnetBinaryPV R Time_Delay Unsigned Notification_Class Unsigned Alarm_Value...

Page 111: ...aracterString R Protocol_Version Unsigned R Protocol_Conformance_Class Unsigned 1 6 R Protocol_Services_Supported BACnetServiceSupported R Protocol_Object_Types_Sup ported BACnetObjectTypesSupported R Object_List BACnetARRAY N of BACne tObjectIdentifier R Max_APDU_Length_Accepted Unsigtned R Segmentation_Supported BACnetSegmentation R VT_Class_Supported List of BACnetVTClass Active_VT_Sessions Lis...

Page 112: ...Unsigned 1 127 Max_Info_Frames Unsigned Device_Address_Binding List of BACnetAddressBinding R Database_Revision Unsigned R Configuration_Files BACnetARRAY N of BACne tObjectIdentifier Last_Restore_Time BACnetDateTime Backup_Failure_Timeout Unsigned16 Active_COV_Subscriptions List of BACnetCOVSubscription Profile_Name CharacterString R ...

Page 113: ... O Status_Flags BACnetStatusFlags R R Event_State BACnetEventState R R Reliability BACnetReliability O2 Out_Of_Service Boolean R R Number_Of_States Unsigned R R State_Text BACnetARRAY N of Charac terString O Time_Delay Unsigned O3 Notification_Class Unsigned O3 Alarm_Values List of Unsigned O3 Fault_Values List of Unsigned O3 Event_Enable BACnetEventTransitionBits O3 Acked_Transitions BACnetEventT...

Page 114: ...lags R R Event_State BACnetEventState R R Reliability BACnetReliability O Out_Of_Service Boolean R R Number_Of_States Unsigned R R State_Text BACnetARRAY N of Charac terString O Priority_Array BACnetPriorityArray R Relinquish_Default Unsigned R Time_Delay Unsigned O1 Notification_Class Unsigned O1 Feedback_Value Unsigned O1 Event_Enable BACnetEventTransitionBits O1 Acked_Transitions BACnetEventTra...

Page 115: ...ent from the property Property 2 Invalid_Datatype 9 Request to access to a specified index outside the array index range Property 2 Invalid_Array_Index 42 Request to write a value outside the permissible range Property 2 Value_Out_Of_Range 37 A COV registration request of more than 10 regis tration items Resource 3 Other 0 An Event registration request of more than 10 registration items Resource 3...

Page 116: ...er shortage occurred during the execution of the service Missing_Required_Parameter 5 Too many arguments for the execution of the service Too_Many_Arguments 7 An attempt to execute an unsupported service with confir mation Unrecognized_Service 9 Abort PDU Reject PDU Reject Reason Unable to process due to too many requests beyond the capacity Buffer_Overflow 1 The processing of segments was aborted...

Page 117: ...he interference at his own expense Caution Changes or modifications not expressly approved by the manufacturer responsible for compliance could void the user s authority to operate the equipment Disposal of your old appliance 1 When this crossed out wheeled bin symbol is attached to a product it means the product is covered by the European Directive 2002 96 EC 2 All electrical and electronic produ...

Page 118: ...ا ال س ت خ د ا م ي ض م ن ا ل م ح ت و ى ا ل و ق ا ي ة م ن إ ل ح ا ق ا ل ض ر ر ب ا ل م م ت ل ك ا ت و إ ل ى م ا غ ي ر ذ ل ك ھ ذ ا ا ل د ل ي ل م ن أ ج ل س ال م ة م ھ ن د س ي ا ل ت ر ك ي ب و ا ل م س ت خ د م ي ن ي ُ ر ج ى و ض ع ا ل د ل ي ل ف ي م ت ن ا و ل أ ي د ي ج م ي ع ا ل م س ت خ د م ي ن t e n C A B P C A t e n C A B 0 C 7 1 B F N Q P 1 C 7 1 B F N Q P ت ر ج م ة ا ل ت ع ل ي م ا ت ا أل ص ل ي ة ...

Reviews: