66
ENGLISH
FUNCTIONAL SPECIFICATIONS ACP BACnet
Local Definition of Object ID - The instance number is a pair, this consists of the indoor unit No. and
item.
Product Type(Indoor:0, Vent:1, AHU:2, ODU:3, AWHP:4, GENERAL:5)
Example of Point Table
The point table below is passed to BMS, and BMS registers the object.
Case Indoor
Address
Product
Type
Product
No.
Point
No.
Instance No.
Name
0
0
0
1
0x00001(1)
ON/OFF : setting
0
0
0
2
0x00002(2)
ON/OFF : status
1
0
1
1
0x00101(257)
ON/OFF : setting
1
0
1
2
0x00102(258)
ON/OFF : status
15
0
15
1
0x00F01(3841)
ON/OFF : setting
15
0
15
2
0x00F02(3842)
ON/OFF : status
16
0
16
1
0x01001(4097)
ON/OFF : setting
16
0
16
2
0x01002(4098)
ON/OFF : status
255
0
255
1
0x0FF01(65281)
ON/OFF : setting
255
0
255
2
0x0FF02(65282)
ON/OFF : status