83
Appendix
Appendix
5
Voltage controlled active power control P(U)
P(U) End Voltage
(112)
P(U) Start Voltage
(110)
U/Un
P/Pn
P(U) Active Power
(100)
0 %
Name
description
default
Value
Available
Value
uint
P(U) Active
Power
Active power gradient at overvoltage
100
0 ~ 100
%
P(U) Start
Voltage
P(U) function starting voltage (U/Un)
110
100 ~ 120
%
P(U) End
Voltage
P(U) function end voltage (U/Un)
112
100 ~ 120
%
P(U) wait time
Waiting time of active power gradient
1
60
sec