Appendix
140
Due to our policy of continuous product innovation, some specifications may change without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Total Ampacity of Home 8 and PV Inverter is > 200A (Partial Backup)
The Home 8 load center and PV load center require main breakers in their load centers. Also, another
dedicated circuit breaker for the 2 load centers is required and should be located between the SE Box
and the two load centers. The lug kit is only supported in the SE Box, not in this breaker.
1) The total ampacity of the breakers for the Home 8 should not exceed the ampacity of the main
breaker in the SE Box and the ampacity of the breaker in the “A” panel.
2) The total ampacity of the breakers for the PV should not exceed the ampacity of the main
breaker in the SE Box and the ampacity of the main breaker of the Home 8 load center for stable
backup operation and the ampacity of the breaker in the “A” panel.
3) The ampacity of the breaker in the “A” panel should not exceed the ampacity of the main breaker
in the SE Box.
4) The ampacity of the main breaker in the backup panel should not exceed the ampacity of the
main breaker in the SE Box.
5) With any of the above cases, the PV CT should not be located in the SE Box. Extended cables for
the PV CT may be required depending on the installation conditions.
6) In the event there is greater than 200A service capacity, the B panel should have two different
main breakers. One would be the dedicated circuit breaker for the SE Box and the other would be
the dedicated circuit breaker for the non-backup load. The energy meter integrated in the SE Box
supports 400A (2 x 200A CT) measurement. In this case, external CTs are required to measure
the non-backup load. (Do not remove the connector of the internal site net CTs.) The measured
value of external CTs are added to that of the internal CTs.
Smart
Energy Box
Stop
Switch
Home 8
Backup Panel
Backup Load
Non-backup
Panel
AC Power
DC Power
Communication
New or Existing Solar System
PV
inverter
New or Existing Solar System
PV
inverter
New or Existing Solar System
PV
inverter
New or Existing Solar System
PV
inverter
Home 8
PV Sub-panel
with main breaker
Home 8 Sub-panel
with main breaker
Sub-panel with
main breaker
(max 200A)
PV CT
External CT
Home 8
Home 8
A
B