![background image](http://html.mh-extra.com/html/lg/g3f-ad3a/g3f-ad3a_user-manual_209556037.webp)
Chapter 4. FUNCTION BLOCK
4 - 10
4.4 Errors on Function Block
This shows errors and resolutions in accordance with them.
Function block
Read
STAT
No.
Local
/Remote
Descriptions
Initiali-za
tion
Array
type
Single
type
Resolutions
0
Operating with no fault
О
О
О
-
1
The base location number is exceeding
the proper setting range
О
О
О
Correct the number in accordance with the
proper range
(See Section 4.2)
2
H/W error of the base
О
О
О
Contact the service station
3
The slot location number is exceeding
the proper setting range
О
О
О
Set the right number to the slot loading the A/D
conversion module
4
The A/D conversion module on the slot is
empty
О
О
О
Load the A/D conversion module to the specified
slot
5
The module loaded isn't the A/D module
О
О
О
Load the A/D conversion module to the specified
slot
6
The channel number is exceeding the
proper range
-
-
О
Specify the available channel correctly
7
H/W error of the A/D conversion module
О
О
О
Contact the service station
8
The A/D conversion module's shared
memory error
О
О
О
Contact the service station
9
The available channels are not specified
-
О
О
Make a correct specification of the available
channel on the initialize function block
17
Local
Average number exceeding the proper
range
О
-
-
Correct the value to the proper range
(Number: 2 to 255)
128
H/W error of the communication module
for remote
О
О
See the manual for the remote communication
module
129
The base location number is exceeding
the proper setting range
О
О
Correct the number in accordance with the
proper range
(See Section 4.3)
131
The slot location number is exceeding
the proper setting range
О
О
Set the right number to the slot mounting the
A/D conversion module
133
The module loaded isn't the A/D module
О
О
Mount the A/D conversion module to the
specified slot
135
H/W error of the A/D conversion module
О
О
Contact the service station
136
The A/D conversion module's shared
memory error
О
О
Contact the service station
137
The available channels are not specified
-
О
Make a correct specification of the available
channel on the initializing function block
145
Remote
Average number exceeding the proper
range
О
-
-
Correct the value to the proper range
(Number: 2 to 255)