background image

5. TROUBLESHOOTING 

-9-

DEFECT 

EFFECT

CAUSE 

REMEDY

SYSTEM
PARTIALLY OR
COMPLETELY OUT
OF REFRIGERANT
CHARGE

EXCESSIVELY
FULL

HUMIDITY IN THE
SYSTEM

PRESENCE OF AIR
IN THE SYSTEM

BLOCKED
CAPILLARY

MOTOR-
COMPRESSOR
SHORT-CIRCUITED
OR BLOCKED

MOTOR-
COMPRESSOR
DOSE NOT
COMPRESS

NOISY MOTOR-
COMPRESSOR

Evaporator does not frost even
though motor-compressor runs
continually.

This defect is indicated by the
presence of water outside the
refrigerator near the motor caused
by formations of ice on the return
tube.

This defect is indicated by the
partial frosting of the evaporator
and by continual defrosting cycles
determined by the interruption of
the flow of gas on the evaporator.
The motor compressor keeps
running.

Poor performance of the
refrigerant system which is
indicated on the evaporator with a
slight frost which does not freeze
and an excessive overheating of
the condenser and motor-
compressor.

Because of the lack of circulation
Freon® in the system, there is no
frosting of the evaporator, while a
slight overheating of the first spiral
of the condenser is noted.

The system does not work and 
the "OLP" intervenes interrupting
delivery to the motor-compressor.

No frost forms on the evaporator,
even if the motor-compressor is
apparently running regulary.

In case of mechanical failure in the
motor-compressor there in an
excessive noise when the system is
functioning. In case a suspension
spring is unhooked, banging will be
heard and there will be especially
strong vibrations when the system
starts up and stops.

An empty refrigerant system
indicates a leakage of R134a. 
This loss is generally to be looked
for at the soldering points
connecting the various components
or in an eventual hole in the
evaporator made by the user.

If in the refrigerant system a
quantity of R134a is introduced
which is greater than that
indicated, the excess gas does 
not terminate its expansion in 
the evaporator but proceeds into
the return tube.

The refrigerant system is humid
when there is a small percentage
of water present, which, not
completely retained by the
dehydrator filter, enters into
circulation with the Freon® and
freezes at the capillary exit in the
evaporator.

There is air in the refrigerating
system when during the filling
phase vacuum is not effected or it
is not adequately done. 

Impurities contained in the Freon®
or in the components of the
refrigeration system before
assembly and not retained by the
filter can obstruct the capillary.

In case of short circuit, the
breakdown is due to the electric
winding. If blocked, there is a
mechanical failure in the motor-
compressor.

In this case there is a mechanical
failure in the diaphram valves which
remaining continually open, do not
permit the compressor to operate. 
Consequentely, Freon® does not
circulate in the system.

The cause of the excessive noise
is normally to be sought for in a
mechanical breakdown, and only
rarely in the unhooking of one of
the suspension springs.

Leakage must be eliminated by
resoldering the defective point or
substituting the damaged
evaporator. 

The system must be emptied and
subsequently refilled introducing
the correct quantity of R134a.

The system must be emptied and
then refilled after eliminating the
humidity.

Group must be drained and
subsequently refilled after
carefully creating vacuum.

To restore the system it must be
emptied, substitute the capillary or
the evaporator entirely in case the
capillary is coaxial with respect to
the return tube, then refill it.

The motor-compressor must be
replaced and then proceed with
refilling.

The motor-comprossor must be
replaced and then proceed with
refilling.

The motor-compressor must be
replaced and then proceed with
the refilling.

Summary of Contents for GC-181SA.CSWQRAN

Page 1: ...REFRIGERATOR SERVICE MANUAL MODEL GC 181SA CSWQRAN CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL COLOR SUPER WHITE http biz lgservice com ...

Page 2: ...set especially thin plate type ex glass plates or books 8 When servicing evaporator part wear cotton gloves to prevent injury by sharp fins of the evaporator 9 Do not open the sealed refrigeration system It could cause injury or pollute the air Leave this job to an autherized servicer with the appropriate refrigerant recovery equipment AIR RECHARGING IN COMPRESSOR Test the refrigeration system by ...

Page 3: ...linder and must add 165 grams to the group this amount will be reached when R134a has dropped to 585 grams remembering that the indicator shows a lower limit of meniscus Do this after choosing the scale corresponding to the gas pressure different scales reported as the same gas pressure indicated by the pressure gauge on the top of the column To make R134a flow into the system open the valve place...

Page 4: ...5g LUBRICANT OIL FREOL 15G 210cc EVAPORATOR Door Inside The heart of the refrigerator It evaporates the refrigerant fluid and thereby absorbs heat from the surrounding area ICE CUBE TRAY Door Inside Ice cube is easy to remove from the tray DRIP TRAY Catches the water that drips off the evaporator when defrosting SHELVES MAGNETIC GASKET Tight fitting door seal keeps all the cooling power locked ins...

Page 5: ... position Adjust the Leveling screw to make sure the appliance is steady and check that the door opens and closes properly Figure 7 B EVA DOOR 1 Open the EVA DOOR and Grasp the Bottom side of the EVA DOOR Hinge 2 Take it out forwards by lifting it slightly up ý Reversible 3 Rotate the EVA DOOR 180 degrees and insert EVA DOOR to opposite side top hole first then in to the Bottom side hole 4 Check t...

Page 6: ...rator 3 Separate Cover Lamp by twisting up and down Figure 11 4 Loosen 1 screw holding the case to remove the Thermostat Enclosure Figure 12 5 Pull Knob Dial 6 Pull out thermostat in the thermostat cover and disconnect wires Figure 13 NOTE Replace a proper specification new thermostat Figure 13 Figure 10 1 2 Figure 9 Figure 11 Figure 12 C TOP TABLE 1 Unscrew 2 bolts at the rear of top table 2 Hold...

Page 7: ...on of the single phase induction motor in the starting operation flows in both main coil and sub coil After the starting is over the current in subcoil is cut off The proper features of PTC play all the above roles So PTC is used as a motor starting device 3 PTC Applied Circuit Diagram According to Starting Method for the Motor 4 Motor Restarting and PTC Cooling 1 For restarting after power off du...

Page 8: ...current in Compressor Motor in case of over rising temperature by Bimetal in the OLP 2 When over voltage flows to Compressor motor the Bimetal works by heating the heater inside the OLP and the OLP protects Motor by cutting off current which flows to the Compressor Motor 2 Role of the OLP 1 The OLP is attached to the Hermetic Compressor used for the Refrigerator and Show Case and prevents the Moto...

Page 9: ... in the refrigerant system a quantity of R134a is introduced which is greater than that indicated the excess gas does not terminate its expansion in the evaporator but proceeds into the return tube The refrigerant system is humid when there is a small percentage of water present which not completely retained by the dehydrator filter enters into circulation with the Freon and freezes at the capilla...

Page 10: ...acting point Shorted or Broken Coil shorted Low voltage Increase the voltage Replace the device Replace the Compressor Repair the Compressor Repair the Compressor Shorted Poor contacting point and broken Shorted The coil of the Compressor Motor is worn out Refrigerant leaks Poor compressing Check the current flowing of starting system Check the components on the main circuit Check if the current f...

Page 11: ...ltage Rating voltage 10 Advice the customer to use in the specified range Advice the customer to use in the specified range Measure minimum starting voltage after checking steps 1 3 above Measure the pressure balance of the PTC at the interval of more than 5 min Starts at the voltage of more than 90 Replace OLP Normal Normal Replace the PTC Replace the PTC STARTER The applied voltage is not in the...

Page 12: ... PTC with a multitester or Wheatstone Bridge Observation value is 220 240V 50Hz 33Ω 30 The value is 0 The value is Check another electric components Replace the PTC Normal Abnormal Abnormal Replace the PTC Separate the OLP from the Compressor and check resistance value between two terminals of OLP with Tester Check other electric components Replace OLP ...

Page 13: ...5 EXPLODED VIEW 13 411A 310A 309A 308A 307A 312A 315A 127A 104A 314A 283B 410A 410G 323B 106B 107A 281B 302A 302B 107B 282D 282D 318A 317A ...

Page 14: ... 14 120D 110C 408B 110A 302C 406B 409B 120A 110B 155A 151A 237A 235A 241C 233A 231A 281D 230A 241A 136B 136B 136A 140A 140A 126A 125A 136A EXPLODED VIEW ...

Page 15: ......

Reviews: