10
•
A multiplying factor is required for increa-
sed output of the photovoltaic modules.
Under normal conditions, a photovoltaic
module is likely to experience conditions
that produce more current and/or voltage
than reported at standard test conditions.
Accordingly, the values of Isc and Voc
marked on this photovoltaic module
should be multiplied by a factor of 125 %
when determining component voltage
ratings, conductor ampacities, fuse sizes,
and size of controls to the photovoltaic
output.
•
Depending on national directives additio-
nal safety factors might be applicable for
overcurrent protection.
General Wiring
•
LG Electronics recommends that all
wiring be double insulated with a mini-
mum rating of 90 °C.
•
All wiring should use a flexible copper
(Cu) conductor.
•
The minimum size should be determi-
ned by the applicable codes. LG
Electronics recommends a size not
smaller than 4 mm
2
.
ELECTRICAL INSTALLATION
Parallel connection for more current