8. Group Control
9. Two Thermistor system
10. High-Static Motor Connection (For 60K/48K Model)
19
ENGLISH
It operates maximum 16 Units by only one Wired Remote Controller,
and each Unit starts sequentially to prevent overcurrent.
• Open the rear cover of Remote
Controller to set up the mode.
• Selectable options are three as follows.
- Remo: Sensing the room Temperature.
- Indoor Unit: Sensing the intake air into
indoor Unit.
- 2 TH: Sensing the lower temperature of
the two thermistors.
• To set up the mode, adjust the slide
switch to desired mode position on
installing.
• Using the supplied Wired Remote Controller,
wire them like above.
• Remove the OP7 resistor.
(Use soldering Iron or others)
• Ensure that the color of wire.
• If working condition of indoor unit is higher than that of standard
static pressure (10mmAq) change the Indoor Motor wire housing
for standard motor housing for higher external static Pressure
(15mmAq).
Operation unit
ZONE
1 2 3 4
Humidify
JET
AUTO
AUTO SWING
OPERATION
FAN SPEED
Program set
SUB FUNCTION
SET TEMP
Room Temp
HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01
03
05
07
09
11
13
15
17
19
21
23
Indoor Unit 1
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Main PCB
#1
Main PCB
#2
Main PCB
#16
Wired Remote Controller
(Standard)
Slide Switch
OP7
Remote
Controller
PCB
Indoor Unit 2
Main PCB
Indoor Unit 16
Connector
RED(12V)
YL(SIGNAL)
YL(SIGNAL)
YL(SIGNAL)
BR(GND)
BR(GND)
BR(GND)
Connecting Cable(Local Supply)
Connector
Connector
....
....
Slide Switch
Remo.
Room Temp. Sensing
Indoor Unit
2 TH(Remo.+Indoor)
• On installing, don't impact to the PCB
and LCD display.
• Don't remove the protection sheet.
• Use the specified screw.
• On installing, turn off the main power.
CAUTION
Control box
Wire Color(YL, BK, BL, OR)
For Higher E.S.P(15mmAq)
Wire Color(BK, BL, RD, OR)
For Standard E.S.P(10mmAq)