User setting
- Movement path :
44
4. CONTROL SYSTEM
ENGLISH
Figure 28 User setting menu
Operation mode setting screen consists of a menu to select the operation mode classified as Local, Scheduled and
Remote, and another menu to select ice making mode or air conditioning mode.
But, in the system function setting, the "Select operation mode" menu is displayed only in the ice making mode.
(1) Operation mode selection
- Local: It is the mode to Run/Stop the chiller using the Run/stop key in the micom control panel at the site
where the chiller is installed.
- Remote: It is the mode to Run /Stop the chiller using remote Run /stop signal (No voltage contact signal:
switch, relay contact signal) in the remote place.
- Scheduled: It is the mode to Run/Stop the chiller automatically following the scheduled program which was
set in the 'Scheduled operation setting' menu where user set the chiller Run /Stop time and
temperature.(Refer to "Scheduled operation setting")
(2) Control mode selection
This menu can be used for the chiller which is manufactured for the ice storage system purpose where ice
making is possible.
In the system function setting, the menu shows up when ice making mode is used. When ice making mode is
not used, the menu does not show up.
- Air conditioning: It is the standard chiller operation mode operated in normal temperature. (7~12 °C)
- Ice making: It is the low temperature chiller control mode in the low temperature. (-5~0 °C)
(3) Other user settings
Menu to set the functions to operate the chiller and input initial set values
This menu is for setting the basic control values of the chiller. If you move cursor to an item which you want to
set in the menu bar, and press 'Select' key, then the key menu will alternate through Previous, Next, Decrease,
Increase with the cursor blinking on the set value.
Use buttons to move, and when you select a
menu, you can change the set values.