4. CONTROL SYSTEM
71
ENGLISH
Classification
Contents
Cause
Operation Status
Switch
contact
Motor status contact - Open
Motor status contact(MP) -
Open
Chiller stop
Problem
Motor over-current abnor-
mal contact - Open
Motor over-current abnor-
mal contact (X1) - Open
Chiller stop
Problem
External fault signal con-
tact – Closed
External fault signal contact
(E-SP) – Closed
Chiller stop
Problem
Startup failure
Compressor startup com-
plete input signal - None
Chiller stop
Problem
Delta contactor (during oper-
ation)- Open
Starter Panel
contactor(KM3) (during Op-
eration) - Open
Chiller stop
Problem
Oil level switch – Open
Oil level switch(OL) – Open Chiller stop
Problem
Refrigerant pressure
switch – Open
Refrigerant pressure
switch(PS) – Open
Chiller stop
Problem
Classification
Contents
Cause
Operation
Status
Preventive
control
Prevent Condenser
high pressure
Close guide vane when Condenser
pressure is above High pressure
prevention set value +(100-set
value)/2
삭제
Display caution message for
Condenser high pressure
preventive control
Caution
Prevent Evaporator
low pressure
Close guide vane when Evaporator
pressure is below Low pressure
prevention set value -(100-set
value)/2
삭제
Display caution message for
Evaporator low pressure
preventive control
Caution
Prevent Evaporator
refrigerant low tem-
perature
Close guide vane when Evaporator
temperature is below Low temper-
ature prevention set value -(100-set
value)/2
삭제
Display caution message for
Evaporator refrigerant low
temperature preventive con-
trol
Caution
Prevent Compressor
discharge high tem-
perature
Close guide vane when Evaporator
temperature is above High temper-
ature prevention set value +(100-
set value)/2
삭제
Display caution message for
Compressor discharge high
temperature preventive con-
trol
Caution
Motor over-current
preventive control
Close guide vane to lower the cur-
rent below the set value when
Compressor motor current reaches
*105% of the set value
삭제
Display warning message
for Compressor motor over-
current preventive control
Caution
Table 10 Protection logics