- 24 -
8. Troubleshooting With Error Display
0
Short
Open
Normal
Change the sensor
possible open harness
in cabinet
Check the Temp and
resistance (Table-1)
Result
SVC Action
8-1 Freezer Sensor Error (Er FS)
No
1
2
Checking flow
Check for a loose connection.
Check the Blue/White to
Blue/White.
Result & SVC Action
<CON7>
<Temperature table-1>
(1) To (2)
-22°F
°C
-13°F
°C
-4°F
°C
5°F
°C
14°F
°C
23°F
°C
32°F
°C
Result
40
30
23
17
13
10
8
The sensor is determined by
the temperature.
For example, 23
indicates -4°F.