9-7 Poor cooling in Freezer compratment
No
1
Checking flow
Check the sensor resistance.
2
Reset the unit and
Input Test 1 Mode.
(Push the button 1 time)
3
Open the freezer door and Check the air
flow.
The sensor is determined by
the temperature.
For example, 23
indicates -4°F.
Result & SVC Action
<CON7>
Status
Windy
No windy
SVC Action
Go to the 4
Check the F Fan motor
4
Check the air temperature.
Cold or not ?
Status
Cold
Not cold
SVC Action
Explain to customer
Check the Compressor
And sealed system
(1) To (2)
-22°F
°C
-13°F
°C
-4°F
°C
5°F
°C
14°F
°C
23°F
°C
32°F
°C
Result
40
30
23
17
13
10
8