Mechanical Installation

Mounting Methods

General Information

Select the appropriate orientation to maximize

sunlight exposure.

In order to prevent water from entering the

junction box, which could present a safety hazard,

module should not be mounted such that the

front/top glass faces downward.

Clearance between the solar module frames and

structures such as roofs or ground is required to

prevent wiring damage and to allow air to

circulate behind the solar module. The

recommended standoff height is a minimum of

100mm.

When installed on a roof, the solar module must

be mounted over a fire-resistant roof covering

rated for the application. The fire resistance of the

solar module from LG Electronics is class C after

ANSI/UL790.

The solar module is only IEC listed for use when

its factory frame is fully intact.

Do not remove or alter the solar module frame.

Creating additional mounting holes may damage

the solar module and reduce the strength of the

frame.

A 6mm gap between module frames should be     

allowed to avoid tension from thermal expansion.

The solar module may be mounted using the

   following methods: (*Torque:8~12Nm )

When installing modules in heavy snow areas,

special care should be taken to install the

modules in a manner that provides sufficient

design strength while meeting local code

requirements.

Mounting by using frame bolts holes

Secure the solar module to the structure using

the factory mounting holes.

Four M8 stainless steel bolts, four nuts, four

spring washers, and eight flat washers are

recommended per solar module.

The module may be fastened to a support using

both the outer and inner bolt holes of the frame.

Each module should be securely fastened at a

minimum 4 points on two opposite sides.

Specific information on the solar module

dimensions and location of mounting holes is

provided in ‘Product Specifications’.

Tighten the bolt securely using this combination.

Place spring washer between Flat washer and

Nut.

Mounting

* Mounting Rails Material : Aluminum, Stainless steel, etc.

 → 

We recommend more than 40x40mm mounting rails.

by using clip or clamps

The module may be fastened to a support using

clips or clamps on both the long edge and the

short edge of the modules.

Specific information on location of clamping

   is provided in ‘Mechanical Installation Scene’

   (Refer Appendix.).

The module frame must overlap more than 15mm.

Clamp system requirements

Clamp width is more than 40mm, depth is more

than 10mm. Clamp height compliant with a frame

height.

The clamp should not be touched with the

module’s glass.

Use corrosion resistant material clamps and

hardware.(If you use a special clamp, it needs to

test for compatibility by LGE.)

Use appropriate bolted connections as per clamp

manufacturer’s instructions.

Follow the clamp manufacturer’s recommended

applied torque to fasten the clamps.

7

Module frame

Bolt

Flat washer

Flat washer

Spring washer

Nut

Mounting Rail

Summary of Contents for LG330N1C-A5

Page 1: ...ully before operating your set and retain it for future reference www lg solar com Installation manual PV Solar MODULE P NO MFL69654303 Rev 01 P TYPE MODELS LGXXXS1C W A5 LGXXXS2W A5 W5 N TYPE MODELS LGXXXN1C W K A5 LGXXXN2C W K A5 ...

Page 2: ...t Specifications 8 6 Disclaimer of Liability Disposal 11 7 Transporting and Storage 11 8 Appendix 12 Revisions Table Date Version Description of change Remark 2016 09 27 1 0 1st edition 2016 11 30 2 0 Add N Type Products 2017 01 10 3 0 Add P Type Product 302W Edit to Modules CAD Drawings 2 2017 03 22 4 0 Add P Type Product W5 Model ...

Page 3: ...Cable bending radius should be more than 4 times the cable diameter at least Please use proper equipment connector wire and buttress for system configuration of the module It may result in damage or failure of the product Do not perform installation in rainy heavily windy or snowy days It may result in safety accident Do not make holes in the frame or glass of the module It may decrease the streng...

Page 4: ...in the carton until the time of installation Make sure flammable gases are not generated near the installation site Do not work alone Please work as part of a team of two or more people Wear a safety belt if working high above the ground Contact with electrically active parts of the panels such as terminals can result in burns sparks and lethal shock whether the panel is connected or disconnected ...

Page 5: ...duce the desired voltage output The current of each module connected in series should be same The maximum number of series connected modules can be determined by basis on max system voltage the 125 safety factor and the module Voc which can be checked in Product Specifications in this document The maximum solar module configuration can be found in Product Specifications Series connection for more ...

Page 6: ...ar washer Cup washer Grounding wire Spring washer Nut Flat washer 6 Module Mounting The LG Electronics LGE Limited Warranty for solar modules is contingent upon modules being mounted in accordance with the requirements described in this section The solar modules are in Application Class A and have the Safety Class II Therefore they can be operated in systems with 120 V DC and higher General access...

Page 7: ... bolts holes Secure the solar module to the structure using the factory mounting holes Four M8 stainless steel bolts four nuts four spring washers and eight flat washers are recommended per solar module The module may be fastened to a support using both the outer and inner bolt holes of the frame Each module should be securely fastened at a minimum 4 points on two opposite sides Specific informati...

Page 8: ...Yes 315 39 8 10 22 32 7 9 64 20 20 1000 MC4 JM601A 1686 1016 40 18 0 LG320S1C W A5 Yes 320 40 1 10 27 33 1 9 68 19 20 1000 MC4 JM601A 1686 1016 40 18 0 LG335S2W A5 W5 Yes 335 45 8 9 86 36 0 9 31 17 20 1000 MC4 JM601A 2024 1024 40 21 7 LG340S2W A5 W5 Yes 340 45 9 9 91 36 4 9 35 17 20 1000 MC4 JM601A 2024 1024 40 21 7 LG345S2W A5 W5 Yes 345 46 1 9 96 36 7 9 41 17 20 1000 MC4 JM601A 2024 1024 40 21 7...

Page 9: ... m2 Cell temp 25 1 5AM LGXXXN1C W A5 LGXXXN1K A5 LG360N2C W A5 LG365N2C W A5 LG370N2C W A5 LG375N2C W A5 LG380N2C W A5 LG385N2C W A5 LG390N2C W A5 LG395N2C W A5 LG400N2C W A5 Yes 360 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 48 5 10 19 37 4 9 63 16 20 1000 MC4 JM601A 05 8 2024 1024 40 21 7 Yes 365 48 6 10 19 37 8 9 66 16 20 1000 MC4 JM601A 05 8 2024 1024 40 21 7 Yes 3...

Page 10: ...Product Specifications Dimensions of Modules 10 60Cell Module 72Cell Module Unit mm in ...

Page 11: ... stream 2 Old electrical products can contain hazardous substances so correct disposal of your old appliance will help prevent potential negative consequences for the environment and human health Your old appliance may contain reusable parts that could be used to repair other products and other valuable materials that can be recycled to conserve limited resources 3 You can take your appliance eith...

Page 12: ...Fig 6 Clamping Type A B B A C C B A 4 point installation is allowed in the following cases 1 Slope roof If module is installed parallel to the rooftop d n i w s a h c u s d n a t s l a n o i t i d d a n a h t i w d e l l a t s n i f I f o o r t a l F 2 A 200mm B 400mm Front 6000Pa Rear 5400Pa m m 0 2 1 A 4point Front 1800Pa Rear 1800Pa C 120mm Front 3200Pa Rear 1800Pa A 120mm m m 0 0 1 3 4 8 B 6po...

Page 13: ...C C B A 4 point installation is allowed in the following cases 1 Slope roof If module is installed parallel to the rooftop d n i w s a h c u s d n a t s l a n o i t i d d a n a h t i w d e l l a t s n i f I f o o r t a l F 2 A 250mm B 400mm Front 5400Pa Rear 4300Pa m m 0 2 1 A 4point Front 1600Pa Rear 1600Pa C 120mm Front 3200Pa Rear 1600Pa A 120mm m m 0 0 1 12 0 1 B 6point Front 5400Pa Rear 4300P...

Page 14: ...st Fig7 Bolting Type 812mm Front 2000Pa Rear 1750Pa Note When installed Fig 7 follow the tracker manufacturer s recommended applied torque and materials to fasten Only Tracker Module frame Bolt Flat washer Flat washer Spring washer Nut Mounting Rail Four M8 5 16inch stainless steel bolts four nuts four spring washers and eight flat washers are recommended per solar module Bolting Method the module...

Page 15: ...oui daero Yeongdeungpo gu Seoul 150 721 Korea Contact solarinfo lge com http www lg solar com This document is subject to change without notice LG LG logo and Life s Good are trademarks of LG Electronics Inc worldwide Trademarks and intellectual properties of LG Electronics Inc are protected by international copyright laws Document II A5 IEC V4 EN 201609 ...