ELECTRICAL SYSTEM INSTALLATION
External Static Pressure Setting Values
External Static Pressure (ESP) Default Settings (NJ frame)
Model Number
Air Volume*
High
Medium
Low
LVN181HV4
640
580
480
LVN241HV4
710
640
480
LVN361HV4
990
880
800
Table 17: ESP Setting Values (NJ frame).
*Installer settings available to change the CFM to 10% above or 10% below the values mentioned in the above table.
How to Enter Installer Setting Mode
1. Press
button and
button simultaneously for 3 seconds to enter the installer
setting mode.
2. When entering installer setting mode, fuction code is displayed on the LCD screen.
3. Press
button to select function code 64 (target air volume).
4. Press
buttons to change value as desired (00 = Default; 01 = +10%; 02 = -10%).
5. Press
button to set value.
6. Press
button and
button simultaneously for 3 seconds to exit installer
setting mode.
Follow this procedure to enter installer setting mode and set the target air volume as desired.