FINAL INSTALLATION PROCEDURES
Pump Down, Cooling Only Mode
Perform Pump Down procedure in the cooling only mode.
Disabling Cooling Only Mode
After Pump Down procedure has been performed, you will need
to disable Cooling Only Mode, and place the unit back into normal
operating mode. Follow the procedure below.
1. Shut down power to system completely.
2. Enter the Installer Mode.
3. Set code to 46.
4. Press Power-ON button and select the code number 46.
• Unit must beep to acknowledge that code has been received.
5. Turn off power.
• Let unit cycle off for a minimum of 30 seconds.
6. Turn power back on to system.
Pump Down Procedure
This procedure is performed when the refrigerant piping system is serviced. Pumping down pushes all the refrigerant into the outdoor unit
without losing any charge. Always adhere to and be familiar with local codes regarding the handling of refrigerant.
The system must operate in cooling only mode to proceed with the pump down procedure. If needed, refer to the sections below for proper
steps to place the unit into cooling only mode.
1. Connect a low-pressure gauge with manifold hose to the charge port on the gas line service valve.
2. Open the gas line service valve halfway.
3. Purge the air in the manifold hose using the refrigerant.
4. Close the liquid line service valve all the way.
5. Turn on the unit’s power switch and start the cooling mode operation.
6. Observe the pressure gauge reading. When it changes 1 to 0.5 kg/cm
2
(14.2 to 7.1 psig), fully close the gas line valve and then immedi-
ately turn the unit off. Pump down procedure is complete and all refrigerant must be collected into the outdoor unit.
Enabling Cooling Only Mode
Before running the Pump Down procedure, you must place the unit
into Cooling Only Mode. In order to be able to run Cooling Only
Mode, you must enter the unit into the Installer Mode by pressing the
Reset button and the JET MODE button simultaneously.
1. Shut down power to system completely.
2. Enter the Installer Mode as stated in the paragraph above.
3. Set code to 45.
4. Press Power-ON button and select the code number 45.
• Unit must beep to acknowledge that code has been received.
5. Turn off power.
• Let unit cycle off for a minimum of 30 seconds.
6. Turn power back on to system.
• After the system is in Installer Mode (with Cooling Only Mode initiated), automatic operation is suspended.
• After Cooling Only Mode is disabled, the unit will return to normal operation.
• Installer Code cannot be entered if the unit is running. The system must be completely powered off.
• All Installer Code numbers must be entered into the system during Power Off state. (Compete shutdown of the system.)
• WLAN Module’s communication time will lag by about 1 minute after unit is turned back on, and in normal operating mode.
• Entire lock or Mode lock cannot be set if you set heating or automatic operation through the central controller.
Never inhale or handle refrigerant directly. Doing so may cause bodily harm and injury.