2
PARAMETER CODE (HEX)
<Common>
: Area accessible regardless of inverter models (Note 3)
Paramet
er
Address
Parameter Name
Unit
Read/Write
Data Value (Hex)
0x0000
Drive model
-
R
4: SV-iS5
0x0001
Drive capacity
-
R
0: 0.75 1:1.5 2:2.2 3: 3.7
4: 5.5 5: 7.5 6: 11 7: 15 8:
18.5 9: 22 A: 30 B:37 C:45
D: 55 E: 75 F: 90 10: 110
11: 132 12: 160 13: 200
14:220 15:280 16:375 (Unit
: kW)
0x0002
Drive Input Voltage
-
R
0: 220V 1: 440V
0x0003
S/W Version
-
R
0100: Ver. 1.00,
0101: Ver 1.01
0x0005
Frequency
Reference
0.01Hz
R/W
0x0006
Run Command
-
R/W
Bit 0: Stop
Bit 1: Forward Run
Bit 2: Reverse Run
Bit 3: Fault Reset
Bit 4: Emergency Stop
0x0007
Acceleration Time
0.1 sec
R/W
0x0008
Deceleration Time
0.1 sec
R/W
0x0009
Output Current
0.1 A
R
9
modbus-rtu iS5 manual.doc