44
Outdoor Unit
u
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction
Factor) value of indoor unit.
Additional
charge(kg)
+
+
+
=
+
Total liquid pipe
:Ø25.4 mm
Total liquid pipe
:Ø22.2 mm
Total liquid pipe
:Ø19.05 mm
Total liquid pipe
:Ø15.88 mm
Total liquid pipe
:Ø12.7 mm
Total liquid pipe
:Ø9.52 mm
Total liquid pipe
:Ø6.35 mm
Number of installed
HR units
+
+
+
CF value of
indoor unit
+
CAUTION
Use only 2-series of indoor unit. Ex) ARNU***2
CF value of indoor unit
(unit : kg)
Capacity(Btu/h(kW))
5k 7k 9k 12k 15k 18k 24k 28k 36k 42k 48k 76k 96k
Type
(1.6) (2.2) (2.8) (3.6) (4.5) (5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28.0)
Ceiling Concealed Duct (Low Static)
-
0.17 0.17 0.17 0.17 0.37 0.37
-
-
-
-
-
-
Ceiling Concealed Duct (High Static)
-
0.26 0.26 0.26 0.26 0.26 0.26 0.44 0.44 0.44 0.62 1.00 1.00
Wall Mounted
-
0.24 0.24 0.24 0.24 0.28 0.28
-
-
-
-
-
-
1Way Ceiling Cassette
-
0.20 0.20 0.20
-
0.29 0.29
-
-
-
-
-
-
2Way Ceiling Cassette
-
-
-
-
-
0.16 0.16
-
-
-
-
-
-
4Way Ceiling Cassette
0.18 0.18 0.25 0.25 0.32 0.32 0.48 0.48 0.64 0.64 0.64
-
-
ARTCOOL Gallery
-
0.10 0.10 0.10
-
-
-
-
-
-
-
-
-
Floor Standing
-
0.17 0.17 0.17 0.17 0.37 0.37
-
-
-
-
-
-
Ceiling & Floor
-
-
0.10 0.10
-
-
-
-
-
-
-
-
-
Ceiling Suspended
-
-
-
-
-
0.35 0.35
-
0.54
-
0.75
-
-
Console
-
0.17 0.17 0.17 0.17
-
-
-
-
-
-
-
-
Fresh Air Intake Unit
-
-
-
-
-
-
-
-
-
-
0.62 1.00 1.00
Heat recovery ventilator(DX)
-
-
-
0.20
-
0.20 0.20
-
-
-
-
-
-
Refrigerant piping system