8
ENGLISH
CAUTION
Be very careful while carrying the product.
• Do not have only one person carry product if it is more than 20kg.
• PP bands are used to pack some products.
Do not use them as a means for transportation because they are
dangerous.
• Tear the plastic packaging bag and scrap it so that children can-
not play with it.
Otherwise plastic packaging bag may suffocate children.
• When carrying in outside unit, be sure to support it at four points.
Carrying in and lifting with 3-point support may make outside unit
unstable, resulting in a fall of it.
• Use 2 belts of at least 8 m long.
• Place extra cloth or boards in the locations where the casing
comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
!
Items
pH(25C)
Conductivity[25C](mS/m)
Chlorine ion(mg CI-/
l
)
Sulfuric acid ion(mg SO
2
-/
l
)
Acid demand[pH 4.8] (mg SiO
2
/
l
)
Total hardness(mg SiO
2
/
l
)
Ca hardness(mg CaCO
3
/
l
)
Ion silica(mg SiO
2
/
l
)
Fe(mg Fe/
l)
Copper(mg Cu/
l)
Sulfuric acid ion(mg S
2
/
l)
Ammonium ion(mg NH
4
/
l)
Residual chlorine(mg Cl/
l)
Free carbon dioxide(mg CO
2
/
l)
Stability index
7.0~8.0
Below 30
Below 50
Below 50
Below 50
Below 70
Below 50
Below 30
Below 1.0
Below 1.0
Must not be detected
Below 0.3
Below 0.25
Below 0.4
-
Below 0.3
Below 0.1
Must not be detected
Below 0.1
Below 0.3
Below 4.0
-
7.0~8.0
Below 30
Below 50
Below 50
Below 50
Below 70
Below 50
Below 30
O
O
O
O
-
-
-
-
O
O
O
O
O
O
O
O
-
-
-
-
-
O
O
O
-
O
O
O
O
O
Closed type
Basic Item
Reference Item
Effect
Circulating water
Supplemented water
Corrosion
Scale
4
+
Reference
• The "O" mark for corrosion and scale means that there is possi-
bility of occurrence.
• When the water temperature is 40°C or above or when un-
coated iron is exposed to the water, it can result in corrosion.
Therefore adding anti-corrosion agent or removing the air can be
very effective.
• In case of using the closed type cooling tower, the cooling water
and supplementing water must satisfy the water quality criteria
of closed type system in the table.
• Supplementing water and supplied water must be supplied with
tap water, industrial water and underground water excluding fil-
tered water, neutral water, soft water etc.
• 15 items in the table are general causes of corrosion and scale.
LIFTING METHOD
- When carrying the unit suspended, pass the ropes under the unit and
use the two suspension points each at the front and rear.
- Always lift the unit with ropes attached at fours points so that impact
is not applied to the unit.
- Attach the ropes to the unit at an angle of 40° or less
Sub line
40° or less
Rope supporter
A
B
WARNING
The location of the Anchor bolts
• Install at places where it can endure the weight and vibration/noise
of the outside unit .
• The outside unit supports at the bottom shall have width of at least
100mm under the Unit’s legs before being fixed.
• The outside unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
At least 100mm
At least 100mm
At least 100mm
At least 100mm
The location of
anchor bolt
62
62
631
755
500
472
INSTALLATION
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall
down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is
transferred through the installation part depending on installation sta-
tus. Thus, use anti-vibration materials (cushion pad) fully (The base
pad shall be more than 200mm).
At least
200mm
Summary of Contents for Multi V ARWN Series
Page 37: ......