31
Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
AHU COMMUNICATIONS KIT INSTALLATION
Communication Module
RS485 Communication Port
NTCThermistor
RemoteController
Electronic Expansion Valve
Note :
Whenacommunicationmodule(orPAHCMR000)isconnectedtothemainmoduleofPAHCMS000,DOandUIincommunication
module are not used.
Name
Port
Item
Electrical Spec.
Function
EEV
12 VDC/1/2/3/4
EEV Control
Max32.8ft
EEV Control
Name
Port
Item
Electrical Spec.
Function
REMO
+12V/SIG/GND
Wire Remote
Controller
Max 164 ft
Communication with Wired Remote Controller
Name
Port
Item
Electrical Spec.
Function
Thermistor
Discharge
NTC RI2/G
Discharge air Thermistor
NTC10k
Ω,
16.4ft
Discharge Air temperature sensor
ThermistorPipein
NTC RI3/G
Pipe in (Liquid) Thermistor
NTC5 k
Ω,
16.4 ft
Inlet pipe (Liquid) Temp. sensor
Thermistor Pipe
out
NTC RI4/G
Pipe out(Gas)Thermistor
NTC5 k
Ω,
16.4 ft
Outlet pipe (Gas) Temp. sensor
Name
Port
Item
Electrical Spec.
Function
MULTI V IDU
Comm.
RS485 CH2
MULTI V Comm.
(IDU A/B)
Max 3280 ft,
2C x 18~16 AWG
(shield wire)
Communication with MULTI V
Outdoor unit
Single IDU
Comm.
SINGLE N/SIG
Single split Comm.
(IDU A/B)
Max 246 ft,
2C x 18~16 AWG
(shield wire)
Communication with Single Split
Outdoor unit