COMMUNICATION KIT INSTALLATION
23
E
N
G
L
IS
H
• Dip S/W(SW03) NO 4 : ON
Example) 5.85~6.15 Voltage is recognized as 6.0V.
Analog Input 10-4 (VDC)
Room Temp.(°C)
Cooling
Room Temp.(°C)
Heating
Normal
Range
Min.
Max.
0.5
0
1.15
Not available
Not available
1.5
1.35
1.65
18
16
2
1.85
2.15
18
17
2.5
2.35
2.65
18
18
3
2.85
3.15
19
19
3.5
3.35
3.65
20
20
4
3.85
4.15
21
21
4.5
4.35
4.65
22
22
5
4.85
5.15
23
23
5.5
5.35
5.65
24
24
6
5.85
6.15
25
25
6.5
6.35
6.65
26
26
7
6.85
7.15
27
27
7.5
7.35
7.65
28
28
8
7.85
8.15
29
29
8.5
8.35
8.65
30
30
9.5
8.85
10
Not available
Not available
CAUTION
If you want to control the Room Temperature using Remote controller, you have to be off
the Dip S/W 4 and Dip S/W 6, and setting the Rotary S/W to the ‘0’ .
!