34
TROUBLESHOOTING
E
N
G
L
IS
H
[Error Code (Comm.Kit)]
Display Number
Error Item
Cause of Error
CH
01
Room Temperature
Temperature sensor disconnection or
short circuit on Room or RA of AHU
CH
02
Pipe In Temperature sensor
error
Temperature sensor disconnection or
short circuit on pipe inlet of AHU
CH
03
Communication error between
wired remote controller and
Comm. Kit
No communication signal for more
than 3 minutes from wired remote
controller to the Comm. Kit
CH
05
Communication error between
Comm.
Kit and Outdoor Unit
No communication signal for 5 minutes
continuously from Comm. Kit to Out-
door Unit
CH
06
Pipe Out Temperature sensor
error
Temperature sensor disconnection or
short circuit on pipe outlet of AHU
CH
09
Option PCB EEPROM error
No reading signal for 5 times continu-
ously from EEPROM to Comm. Kit
Problem
Cause
Remedy
AHU Communication Kit
does not work
No power supply
Check the electrical connection and voltage
of the power supply.
Wiring is wrong
Check the electrical connection of the
Communication Kit (Refer to the circuit dia-
gram of the Communication Kit)
AHU Communication Kit
is broken
Check the electrical and mechanical part.
TROUBLESHOOTING
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condi-
tion.
- Error mark is displayed on wired remote controller, and 7-segment LED of outdoor unit control
board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.