- 32 -
Chiller Water-cooled Screw
No
MODBUS
address
Meaning
Unit Indication
Writing
1
46101
Cooling water outlet
Temperature
Actual Valve X 10[
]
-
2
46102
Cooling water inlet
Temperature
Actual Valve X 10[
]
-
3
46103
Chilled water outlet
Temperature
Actual Valve X 10[
]
-
4
46104
Chilled water inlet
Temperature
Actual Valve X 10[
]
-
5
46105
Compressor motor
Temperature
Actual Valve X 10[
]
-
6
46106
Operation capacity
%
-
7
46107
Compressor current
Ampere
-
8
46108
Chiller operation time
Hour
-
9
46109.0
Chiller Starting
0
OFF
1
ON
-
10
46109.1
Chiller Shut-downing
0
OFF
1
ON
-
11
46109.2
Chiller Stop
0
OFF
1
ON
-
12
46109.3
Chiller Failure
0
OFF
1
ON
-
13
46110.0
Comp Main MC
0
OFF
1
ON
-
14
46110.1
Comp MC
0
OFF
1
ON
-
15
46110.2
Comp Y MC
0
OFF
1
ON
-
16
06111
Start/stop
1
Start
0
Stop
Yes
17
41421
chilled water outlet
setting temperature
Actual Valve X 10[
]
Yes
Table 7
MODBUS address map is shown in the table below.
* Must not use MODBUS mode, when unit is running on local mode.
LGE doesn't have any responsibiliy about problem you disobey