Symptom
Cause
Solution
Compressor is not
operating
Wire open
Control fuse open
High pressure switch (HPS) stop
Connection to terminal in loose
condition
Incorrectly connected controller
Check unconnected part
Check grounded or shorted condition of control
circuit. Replace fuse
Use navigator to initialize current alarm
Check connection from CCP to contactor
Check and reconnect wire
Excessive voltage drop
Check wire voltage
Decide voltage drop location and resolve defect
Compressor motor defect
Check motor coil open or short condition
Replace compressor if necessary
Compressor abnormal stop
Prior lubrication defect.
Replace compressor
Check oil pump operation, check oil pressure
converter, check oil. solenoid valve operation
Abnormally low
pressure stopped
the compressor
operation
Leakage
Defect converter
Insufficient refrigerant
Defective expander
Full/Partial clog in strainer
Repair and recharge leakage part
Replace converter
Add refrigerant
Repair/Replace as needed
Disassemble and clean strainer
Abnormally high
pressure stopped
the compressor
operation
High pressure switch malfunction
Compressor
discharge
valve partially
closed.
Condenser water pipe clogged.
Issue of condenser scale
Replace switch
Open valve or replace valve with defect
Check pipe. Repair or replace defect
Clean condenser
Long
or
continuous chiller
operation
Insufficient refrigerant charged amount
Control fuse issue
Full/Partial clog in strainer
Insulation defect
Service load above design capacity
Inefficient compressor
Add refrigerant
Replace controller
Clean or replace
Replace or repair
Review load condition
Check loader solenoid valve and replace if necessary
Abnormal noise
Pipe vibration
Install support pipe if necessary
Expansio
n
valve noise
Add refrigerant
Check clogged pipe strainer
Compressor noise
Replace compressor (Worn bearing)
Check loose bolt for compressor on the chiller
Oil loss of
compressor
Leakage from system
Mechanical damage of rotor
Identify and repair leakage
Replace compressor
High temperature
pipe
Insufficient refrigerant from leakage
Repair and recharge leakage
Low temperature
pipe
Stop valve is partially closed or limited
Open valve or remove limit
Compressor
loader abnormal
operation
Electronic coil defect
Loading solenoid valve defect
Misconnected solenoid valve
Replace coil
Replace valve
Connect the wire correctly
Table 16