20
Addr
ess
NO.
Description
Default
Maximum
Minimum
Unit
4108
FU1 #08
V/F pattern
0
3
0
4109
FU1 #09
Fwd boost
2
20
0
1 %
410A
FU1 #10
Rev boost
2
20
0
1 %
410B
FU1 #11
Acc. pattern
0
2
0
410C
FU1 #12
Dec. pattern
0
2
0
410D
FU1 #13
Volt control
100
110
40
1 %
410E
FU1 #14
Energy save
100
100
70
1 %
410F
FU1 #15
Stop mode
0
2
0
4110 FU1
#16
User-1f
1000
User-2f
0
0.01Hz
4111
FU1 #17
User-1v
15
User-2v
0
1 %
4112
FU1 #18
User-2f
3000
Freq. max
User-1f
0.01Hz
4113
FU1 #19
User-2v
50
100
User-1v
1 %
4114
FU1 #20
V-I mode
0
3
0
4115
FU1 #21
Filter gain
25
100
1
1 %
4116
FU1 #22
Analog gain
1000
2500
500
0.1 %
4117
FU1 #23
Analog bias
1000
2000
0
0.1 %
4118
FU1 #24
Analog dir
0
1
0
4119
FU1 #25
Freq. limit
0
1
0
411A
FU1 #26
F-limit high
6000
Freq. max
F_limit low
0.01Hz
411B
FU1 #27
F-limit low
0
F-limit high
0
0.01Hz
411C
FU1 #28
Freq. jump
0
1
0
411D
FU1 #29
Freq-jump 1f
1000
Freq. max
0
0.01Hz
411E
FU1 #30
Freq-jump 2f
2000
Freq. max
0
0.01Hz
411F
FU1 #31
Freq-jump 3f
3000
Freq. max
0
0.01Hz
4120
FU1 #32
Freq. band
500
3000
0
0.01Hz
4121
FU1 #33
DC-br freq.
50
6000
0
0.01Hz
4122
FU1 #34
DC-br block
20
50
5
0.1sec
4123
FU1 #35
DC-br time
5
250
1
0.1sec
4124
FU1 #36
DC-br value
1
20
1
1 %
4125
FU1 #37
Slip compen.
0
1
0
4126
FU1 #38
Rated slip
0
500
0
0.01Hz
4127
FU1 #39
M-rated cur.
1
9990
1
0.1 A
4128
FU1 #40
No-load cur.
1
3000
1
0.1 A
4129
FU1 #41
Inv capacity
0
15
0
412A FU1
#42
Retry
number
0
10
0
412B
FU1 #43
Retry time
10
100
0
0.1sec
412C
FU1 #44
Relay mode
0
3
0
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu