Chapter 6 - Parameter Description [I/O]
127
frequencies are applied when the multi-function input
terminals (P1, P2, P3, RST, BX, JOG, FX and RX) select
the step. See [Speed-L, Speed-M, Speed-H, Speed-X] in
I/O-12 ~14, I/O-33.
Step
Freq.
Code Spd-X
Spd-H
(P3)
Spd-
M(P2)
Spd-L
(P1)
Jog
Ter.
Step
Freq-0
DRV-00
0
0
0
0
0
Jog
I/O-20
X
X
X
X
1
Step
Freq-1
DRV-05
0
0
0
1
0
Step
Freq-2
DRV-06
0
0
1
0
0
Step
Freq-3
DRV-07
0
0
1
1
0
Step
Freq-4
I/O-21
0
1
0
0
0
Step
Freq-5
I/O-22
0
1
0
1
0
Step
Freq-6
I/O-23
0
1
1
0
0
Step
Freq-7
I/O-24
0
1
1
1
0
Step
Freq-8
I/O-85
1
0
0
0
0
Step
Freq-9
I/O-86
1
0
0
1
0
Step
Freq-10
I/O-87
1
0
1
0
0
Step
Freq-11
I/O-88
1
0
1
1
0
Step
Freq-12
I/O-89
1
1
0
0
0
Step
Freq-13
I/O-90
1
1
0
1
0
Step
Freq-14
I/O-91
1
1
1
0
0
Step
Freq-15
I/O-92
1
1
1
1
0
7-
0: OFF, 1: ON, X: Jog
** Speed-X: The highest speed input bit (used when one of
RST, BX, JOG, FX, RX set to Speed-X)
☞
I/O-20 [Jog Frequency] can be used as one of the step
frequencies.
☞
If the ‘Jog’ terminal is ON, inverter operates to Jog
frequency regardless of other terminal inputs
.
[‘JOG’ and ‘Multi-Step’ Operation]
I/O-25 ~ I/O-38: 1
st
~ 7
th
Accel/Decel Time
□
□
□
These codes are applied when the multi-function input
terminals (P1, P2, P3) select the Accel/Decel time. See
[XCEL-L, XCEL-M, XCEL-H] in I/O-12 ~ I/O-14.
Related Functions:
DRV-04 [Frequency mode]
DRV-05 ~ DRV-07 [Step Frequency 1 ~ 3]
I/O-12 ~ 14, 93~97 [Multi-function inputs]
I/O-17 [Filtering Time Constant]
I/O? Acc time-1
25 20.0 sec
20.00
25
Factory Default:
20.0 sec
20.0
I/O? Dec time-7
38 20.0 sec
20
38
Factory Default:
20.0 sec
20.0
Related Functions:
DRV-01 ~ DRV-02 [Accel/Decel Time]
FU2-70 [Reference Freq. for Accel/Decel]
FU2-71 [Accel/Decel Time Scale]
I/O-12 ~ I/O-14 [Multi-function inputs]
P1-CM
ON
ON
Output Frequency
Time
Time
P2-CM
ON
ON
Time
P3-CM
ON
Time
JOG-CM
ON
Time
FX-CM
ON
Time
RX-CM
ON
Time
ON
ON
Step
0
Step
1
Step
2
Step
3
Step
4
Step
5
Step
6
Step
7
Jog