Chapter 1 – Installation
13
1.6 Basic Wiring
230/460V
50/60Hz
U
V
W
G ( )
R
S
T
N
1
DB Unit(Optional)
5
DB Resistor
φ
3
MCCB MC
(Option)
FX
RX
BX
RST
P1
P3
CM
VR
V1
I
5G
+
FM
5G
(N.O.) 30 A
AXA
AXC
Output Frequency Meter
(0~10V Linear)
2
P2
MOTOR
Potentiometer
(1 kohm, 1/2W)
Speed signal Input3
Forward Run/Stop
Reverse Run/Stop
Inverter Disable
Fault Reset
Multi-function Input 1
Multi-function Input 2
Multi-function Input 3
Common Terminal
Factory Setting:
‘Speed-L’
‘Speed-M’
‘Speed-H’
Power supply for
speed signal:
+ 12V, 10mA
Speed signal input:
0 ~ 10V
Speed signal input:
4 ~20mA (250ohm)
Common for
VR, V1, I
Fault output relay
less than AC250V, 1A
less than DC30V, 1A
Multi-function output relay1
less than AC250V, 1A
less than DC30V, 1A
Factory setting: ‘Run’
Note) Main Circuit Terminals Control Circuit Terminals.
1. The terminal configuration varies depend on the model number. Please refer to the ‘1.7 Power terminals’.
2. Analog output voltage is adjustable up to 12V.
3. Analog speed command may be set by Voltage, Current or both.
4. The Common Busbar between P1
/L1
and P2/
L2
must be removed before installing DC Reactor.
5. 1 ~ 10 HP inverters have built-in braking circuit. Braking resistors are only included for 1 ~ 5HP inverters.
15~30HP inverters have built-in DB unit.
15 ~ 100 HP inverters need optional braking unit and resistor.
P2/
L2
1
P1/
L1
1
DC Bus Choke (Optional)
4
FM
Dynamic
Braking Unit
(Optional)
P N B1 B2
DC Bus Choke
DB Resistor
JOG
Jog
Shield
(N.C.) 30 B
30 C
Main Power
Circuit
Control Circuit
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu