Chapter 6 - Parameter Description [FU1]
88
[Accel/Decel Pattern: ‘Linear’]
[Accel/Decel Pattern: ‘S-curve’]
[Accel/Decel Pattern: ‘U-curve’]
FU1-07: Stop Mode
Sets the stopping method for the inverter.
Setting Range
LCD
7-Seg
Description
Decel
0
Inverter stops by the deceleration pattern.
Dc-brake
1
Inverter stops with DC injection braking.
Inverter outputs DC voltage when the
frequency reached the DC injection
braking frequency set in FU1-08 during
decelerating.
Free-run
(Coast to stop)
2
Inverter cuts off its output immediately
when the stop signal is commanded.
[Stop Mode: ‘Decel’]
[Stop Mode: ‘D c-brake’]
Output Frequency
Time
Acc. Pattern
Dec. Pattern
Output Frequency
Time
Acc. Pattern
Dec. Pattern
Output Frequency
Time
Acc. Pattern
Dec. Pattern
FU1? Stop mode
07 Decel
0
07
Factory Default:
Decel
0
Output Frequency
Time
FX-CM
ON
Output Voltage
Time
Time
Stop Command
Output Frequency
Time
FX-CM
ON
Output Voltage
Time
Time
Stop Command
FU1-08
FU1-10
[DCBr Value]
t1 t2
t1: FU1-09
t2: FU1-11