18
Air-to-Water Heat Pump
Cycle Diagram
Description
INDOOR UNIT
OUTDOOR UNIT
Indoor Unit
Plate Heat
Exchanger
(Accessories)
Outdoor Unit
EEV
Heat Exchanger
COMPRESSOR
Accumulator
GAS SIDE
LIQUID SIDE
3-Way
Service Valve
3-Way
Service Valve
COOLING
HEATING
Reversing Valve
Pressure
sensor
Th3
Th1
Th2
Th6
Th7
Th8
Th5
Th4
General Information
Category
Symbol
Meaning
PCB
Connector
Remarks
Indoor
Unit
Th1
Remote air temperature sensor
CN_ROOM
- Optional accessory (being sold separately)
- Not shown in diagram
Th2
Inlet evaporator temperature sensor
CN_PIPE
- Meaning is expressed based on Cooling
mode.
Th3
Outlet evaporator temperature sensor
CN_PIPE/O
Outdoor
Unit
Th4
Compressor-suction pipe temperature sensor
CN_TH3
- Th4 and Th5 are connected at 4 pin type con-
nector CN_TH3.
Th5
Compressor-discharge pipe temperature sensor
CN_TH3
Th6
Condenser temperature sensor
CN_TH2
- Description is expressed based on Cooling
mode
- Th6 and Th7 are connected at 4 pin type
connector CN_TH2
Th7
Outdoor air temperature sensor
CN_TH2
Th8
Condenser middle temperature sensor
CN_TH3
- Th8 is connected at 4 pin type connector
CN_TH3
EEV
Electronic Expansion Valve
CN_LEV1
Summary of Contents for Therma V AHUW096A2
Page 97: ......