Piping and Wiring for Outdoor Unit
Connecting Pipe to Outdoor Unit
(Product Heating Capacity : 9kW)
• Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench
until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for tightening fol-
lows the arrow on the wrench.
Align the center of the piping and sufficiently
tighten the flare nut by hand.
mm inch kgf.m
Ø6.35 1/4 1.8~2.5
Ø9.52 3/8 3.4~4.2
Ø12.7 1/2 5.5~6.6
Ø15.88 5/8 6.3~8.2
Ø19.05 3/4 9.9~12.1
Outside diameter
Torque
Torque wrench
Outdoor unit
Gas side piping
Liquid side piping
Installation Manual
43
ENGLISH