Piping and Wiring for Outdoor Unit
Two kind of cables should be connected to the outdoor unit : One is ‘Power cable’, the other one is ‘Connecting cable’.
Power cable is a cable which is used to supply external electricity to the outdoor unit. This cable is generally connected
between external power source (such as main electric power distribution panel of user’s house) and the outdoor unit.
Connecting cable is, on the other hand, used to connect between the outdoor unit and the indoor unit to supply electric
power to the indoor unit and to establish the communication between the outdoor unit and the indoor unit.
Procedure for wiring to the outdoor unit is four steps. Before starting wiring, check if wire specification is suitable and
read following directions and cautions VERY carefully.
Wire Specification
Power Cable Specification :
The power cord connected to the outdoor unit should be complied with
IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or H07RN-F)
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly quali-
fied persons in order to avoid a hazard.
Terminal Specification of Power Cable and related Cautions :
Use round pressure terminals for connections to the power terminal block.
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
Connecting Cable Specification :
The connecting cable, being used to connect the indoor unit and
outdoor unit, should be complied with IEC 60335-1 standard (This equipment shall be provided with
a cord set complying with the national regulation).
Point for attention regarding quality of the public electirc power supply
• In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to
consult the distribution network operator to ensure that the equipment is connected only to a supply
with Zsys≤Zmax, respectively Ssc ≥ minimum Ssc value.
20mm
GN/YL
1 Phase(Ø)
3 Phase(Ø)
20mm
GN/YL
Round pressure terminal
Power wire
20mm
GN/YL
If the supply cable is damaged, it must be replaced by a special cable or as-
sembly available from the manufacturer or its service agent.
Electrical Wiring
44
Air-to-Water Heat Pump
Summary of Contents for Therma V AHUW096A2