Piping and Wiring for Outdoor Unit
• European/International Technical Standard setting the limits for voltage changes, voltage fluctua-
tions and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A.
• European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current ≤16A of
≻
75A per phase.
Circuit Breaker Specification
• Select a power source that is capable of supplying the current required by the AWHP.
• Use a recognized circuit breaker between the power source and the unit.
A disconnection device to adequately disconnect all supply lines must be fitted.
• Capacity of circuit breaker recommended.
• Separate main power supply and heater supply.
Installation Manual
45
ENGLISH
Notes:
1. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
2. Select wire spec. based on the MCA
3. Recommended circuit breaker is ELCB (Earth Leakage Circuit breaker)
4. RLA is measured during each individual compressor test condition.
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating Over current Protective device
RLA : Rated Load Amperes (A)
FLA : Full Load Amperes (A)
S/Heater: Sanitary Water Tan Heater
Model
Core Component Electrical Spec.
MCA, MOP & Circuit Breaker
Compressor
Electric Heater
Sanitary Tank Heater
For
Heat Pump
For Electric Heater
(without S/Heater)
For Electric Heater
(with S/Heater)
Indoor
Outdoor
Power
Supply
RLA
(A)
FLA
(A)
Capacity
(kW)
Power
Supply
RLA
(A)
Capacity
(kW)
Power
Supply
FLA
(A)
MCA
(A)
MOP
(A)
Circuit
Breaker (A)
MCA
(A)
MOP
(A)
Circuit
Breaker (A)
MCA
(A)
MOP
(A)
Circuit
Breaker (A)
AHNW03604A2 AHUW036A2
1~
220-240V
50Hz
8
10
3
1Ø 230V 12.5
9
16.6
20
15
27
30
25
45
40
AHNW09604A2
AHUW056A2
9.7
15
2+2
1Ø 230V
8.3
13
23.9
20
15
27
30
25
45
40
AHUW076A2
AHUW096A2
AHNW16606A2
AHUW126A2
17
25
3+3
12.5
22
40.3
40
23
41
40
29
53
50
AHUW146A2
AHUW166A2
AHNW16809A2
AHUW128A2
3N~
380-415V
50Hz
5.3
9.9
3+3+3 3Ø 400V 8.7
6
11.1
10
12
22
20
21
38
30
AHUW148A2
AHUW168A2
Summary of Contents for Therma V AHUW096A2